Addr
Description
5020
Nominal grid frequency
5021
Nominal grid voltage
5022
Nominal apparent power
capability
5023
Actvie grid type:
0 = grid-tied, 400V, 50Hz
1 = grid-tied, 480V, 60Hz
2 = island mode, 400V,
50Hz
3 = island mode, 480V,
60Hz
4 = grid-tied, 380V, 60Hz
5024
Status of power limiting
controller
0 = inactive,
1 = DC link limiting con-
troller active
2 = grid code limiting
active
3 = overload limiting
active
4 = temperature derating
active
5025
Active DC link reference
voltage
5026
Active DC link min vol-
tage
5027
Active DC link max vol-
tage
5028
Voltrage threshold of DC
link half
5029
Active voltage source
mode, grid-forming:
0 = not grid-forming (grid-
following)
1 = grid-forming
90
Manipulation
Unit
Res
Default
olu-
tion
Hz
0.1
500
V
1.0
400
VA
1.0
25000
-
1.0
0
1.0
0
V
0.1
0
V
0.1
0
V
0.1
0
V
0.01
0
-
1.0
1
Min
Max
Dat
Typ
atyp
e
e
UIN
Regi
T16
ster
UIN
Regi
T16
ster
UIN
Regi
T16
ster
0
UIN
Regi
T16
ster
0
10
UIN
Regi
T16
ster
600
950
UIN
Regi
0
0
T16
ster
600
950
UIN
Regi
0
0
T16
ster
600
960
UIN
Regi
0
0
T16
ster
0
500
UIN
Regi
00
T16
ster
0
1
UIN
Regi
T16
ster
2024-08-01
Len
FCr
FCw
gth
1
04
1
04
1
04
1
04
1
04
1
04
1
04
1
04
1
04
1
04
A67-0141-00.BKfr-0
01-11