Télécharger Imprimer la page

Salicru EMi3 M 5-2 Manuel D'utilisateur page 59

Régulateur de tension à servomoteur

Publicité

Les langues disponibles

Les langues disponibles

4.2. DEFINITION OF THE PRODUCT.
4.2.1. Nomenclature.
EMi3 T 20-2TFMR-BM IR WCO ±20% 3x220V T/T ±4% EE595328
4.3. PRESENTATION.
EMi3 stabilizer model has been designed to operate in fluc-
tuated mains and to safeguard the critical loads, in particular,
those ones with a complicated nature: high inrush start up cur-
rents, high reactive character, high powers, etc. These equip-
ments are very robust against long overloads and they have
a high output accuracy (up to ±1%), they are manufactured
in single and three phase structures with independent phase
regulation or average regulation in the three phases depending
on the model.
Any three phase servomotor stabiliser has only one electronic
control card for all the phases and one LCD panel for its moni-
toring and complete control, less those ones that consist of
three independent single phase equipments duly connected to
make a three phase equipment. In these ones, each cabinet will
have its own electronic control card and its LCD panel.
Depending on the total power of the three phase equipments,
no matter if they include some options or not, they are supplied
assembled in one metallic cabinet, divided in two cabinets
joined together mechanically at factory or by three separate
USER'S MANUAL
EE*
Particular client specifications.
±4%
Output accuracy, if its different from ±1 %.
E/E
Input/ouput configuration, star/star.
E/T
Input/ouput configuration, star/delta.
T/T
Input/ouput configuration,delta/delta.
T/E
Input/ouput configuration,delta/star.
3x220V
Nominal voltage of equipment. Omit for 3x400 V or 230 V.
±20%
Input range, if it is different from ±15 %.
CO
"Made in Spain" marking in the equipment and pack-
aging (custom issue).
W
Neutral brand equipment.
IR
Dry contacts of LCD control panel to terminals.
I
COM card.
BM
Manual bypass.
MR
Max-min output voltage protection with automatic
rearming.
M
Max-min output voltage protection with manual re-
arming.
MRS
Max-min output voltage protection with automatic
rearming and overload protection.
F
Independent phase regulation.
T
Isolation transformer, usually fitted in the output. It
can also be fitted in the input as voltage adaptor or
for changing the voltage configuration, i.e. E/T (star/
delta).
2
First character of the common voltage.
2/4
First character of the input/output voltage.
20
Power in kVA.
M
Single phase equipment.
T
Three phase equipment.
EMi3
Servomotor stabilizer family series.
cabinets, which will be joined after their final location.
The input and output are marked in the terminal strips of the
equipment. When installing the device, use the suitable cross
cable section in order to guarantee its correct operating.
The LCD of the control panel of the stabilizer allows checking
the input/output voltages and frequency, whenever you need.
Also, the LCD has measurements of output current, active and
apparent powers per phase and total, power factor per phase
and total and load percentage per phase. These last measure-
ments are only available when the equipment includes the cur-
rent transformers in each one of the output phases (option).
There are LED indicators to inform about both the status of the
equipment and the possible active alarms.
Single line diagram of a single phase equipment is shown in
Fig. 12 (the three phase structure is similar to it but repeating
the same block per each phase).
59
EMi3 SERVOMOTOR VOLTAGE STABILISER

Publicité