Setting elements
3
Override
2
1
8 9
Coding switches
Function
Type of regulating unit
Type of control
Frost protection
D.h.w. priority (only
RVP210)
RVP210 with boiler temperature control
Regulating unit for d.h.w.
heating
Setting potentiometers
Settings must be determined during the planning phase.
If missing, the following guide values can be used.
Potentio-
Function
meter
Switching differential
with two-position con-
trol
Authority of room
temperature on flow
temperature control
Heating limit for ECO
automatic energy
saver
Max. limitation of flow
or boiler temperature
10/12
16.04.1999
10 11
12
Switch position on the left
Control of a motorized valve
Three-position (modulating)
Yes, frost protection
With priority (absolute)
Underfloor heating systems
and boiler operations: al-
ways set to abs.!
Changeover valve
Setting range
1...20 K
0...100 % authority
OFF = quick setback
is inactive
–10...+8°C (referred
to the room tempera-
ture set value)
10...100 °C
4 319 2697 0 c
1
Opening for time switch
2
LED for "Override"
4
3
Operating mode selector
4
Setting knob for heating curve
5
Setting knob for setback
5
6
Setting knob for d.h.w. temperature (only RVP210)
7
Setting knob for normal room temperature
8
Coding switches
6
9
Setting potentiometer for authority of room tem-
perature and quick setback active / inactive
10 Setting potentiometer for max. limitation of flow or
boiler temperature
7
11 Setting potentiometer for ECO heating limit
12 Setting potentiometer for switching differential
Symbol
Symbol
Switch position on the right
Control of a atmospheric or
forced draught burner
Two-position (on/off)
3Pt.
2Pt.
No, no frost protection
No priority (parallel)
abs.
par.
Charging pump
3Pt.
2Pt.
Guide value
Burner control: 6 K
50 % (quick setback is
active)
–3 K (gives a heating
limit of 17 °C at a room
temperature set value
of 20 °C)
Guide value for under-
floor and ceiling heat-
ing systems:
55 °C max..
Siemens Building Technologies / Landis & Staefa Division
Notes
Plants with no room
unit: setting is inactive
Plants with no outside
detector:
Setting 0...100 % =
quick setback is active
Setting OFF = quick
setback is inactive
OFF = function disabled
OFF = function disabled