mundoclima MUPR-H14 Serie Manuel D'installation Et L'utilisauter page 82

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Step 3: Drill wall hole for connective piping
1. Determine the location of the wall hole based
on the position of the mounting plate. Refer
to Mounting Plate Dimensions.
2. Using a 65mm (2.5in) or 90mm (3.54in)
(depending on models) core drill, drill a
hole in the wall. Make sure that the hole
is drilled at a slight downward angle, so
that the outdoor end of the hole is lower
than the indoor end by about 5mm to
7mm (0.2-0.275in). This will ensure proper
water drainage.
Wall
Indoor
Outdoor
Fig.3.2
NOTE: When the gas side connective pipe is
Φ
16mm (5/8in) or more, the wall hole should
be 90mm (3.54in).
3. Place the protective wall cuff in the hole.
This protects the edges of the hole and
will help seal it when you finish the
installation process.
CAUTION
When drilling the wall hole, make sure
avoid wires, plumbing, and other
to
sensitive components.
MOUNTING PLATE DIMENSIONS
Different models have different mounting plates.
For the convenience of installation, there are
bubble level, carved dimensions on the
mounting plate. Please install the plate and drill
wall hole according to the information of the
mounting plate. See the figures below.
Correct orientation of Mounting Plate
BUBBLE
LEVEL
50
2
100
mm
50
50
100
4
100
4
inch
2
2
4
LIQUID
GAS
mm
inch
150
6
RECOMMAND
Unit: mm
Horizontal direction ruler
100
mm
50
inch
2
4
LIQUID
GAS
BUBBLE
LEVEL
CAUTION: The Bubble level on the mounting
plate can't be removed. If it is broken, make
sure to clean up the leaking liquid.
Indoor unit
outline
pipe hole
65mm
50
838,5
Models 9 / 12
Indoor unit
outline
pipe hole
50
65mm
40
Model 18
Indoor unit
outline
pipe hole
90mm
50
55
1180
Model 24
82
50
2
100
50
4
100
Vertical direction
2
4
ruler
mm
inch
150
6
RECOMMAND
417,7
51
pipe hole
65mm
120
40
512
44
95
1007
587
60
pipe hole
90mm
70
pipe hole
65mm
40