To set the boiler parameters proceed as follows:
hold down the button IP for at least three seconds;
press and hold down the button
When the function is active, the letters "F01" and the value of the selected parameter appear on the display.
Modifying parameters
To scroll the parameters use the buttons +/-
To change the single parameter value use the buttons +/-
N.B.:
the value is automatically saved after about 3 seconds. (Do not press any key until the value starts to blink.)
Parameter description
Type of boiler
F01
10= sealed chamber - 20 = atmospheric chamber
Gas used
F02
00 =NATURAL (METHANE) - 01 =LPG
F03
Hydraulic system
Programmable relay 1 setting
F04
02 =zone system (See SERVICE Instructions)
Programmable relay 2 setting
F05
13 ="cool" function for external conditioning system
(See SERVICE Instructions)
External probe input configuration
F06
(See SERVICE Instructions)
Manufacturer information
F07...F09
Climate controller installation method
00 = on the wall (section 18.2)
F10
01 = Not used.
02 = in the boiler (section 18.1)
F11...F12
Manufacturer information
F13
Max. heating output
F14
Max DHW output
F15
Min. heating output
Maximum heating setpoint setting (°C)
F16
00 = 85°C - 01 = 45°C
F17
Pump overrun time in heating mode (01-240 minutes)
Burner ignition delay in heating mode
F18
(00-10 minutes) - 00=10 seconds
F19
Manufacturer information
F20
Manufacturer information
Anti-legionellosis function
F21
00 = Disabled - 01 = Enabled
F22
Manufacturer information
F23
Maximum DHW setpoint temperature (ACS)
F24
Manufacturer information
F25
No water safety device
F26...F29
Manufacturer information (read-only parameters)
F30
Manufacturer information
F31
Manufacturer information
F32...F41
Diagnostics (See SERVICE Instructions)
Final
Calibration function activation
parameter
(See SERVICE Instructions)
Attention:
do not modify the values of the "Manufacturer information" parameters
INSTRUCTIONS FOR FITTERS
21. PARAMETERS SETTING
and then press
(see figure at the side).
;
;
(0-100%)
(0-100%)
(0-100%)
Impostazioni di fabbrica
140 Fi
240 Fi
280 Fi
10
00 o 01
06
02
04
00
00
00
00
100
100
00
00
03
03
07
00
00
00
65
35
01
--
10
00
--
28
320 Fi
240 i
280 i
20
0
7864176 - en