Installation and Operating Specification EDR
Accuracy and measuring ranges
Pressure measuring range max.
Tolerance zero point max.
Tolerance full scale max.
Resolution
Total of linearity, hysteresis and repeatability max.
Long term stability according to DIN EN 60770
Temperature coefficient typical
Temperature coefficient max.
Temperature coefficient sensitivity typical
Temperature coefficient sensitivity max.
The accuracy data are percentages and refer to the maximum possible
measuring range of the respective type.
Test conditions: 25 °C, 45 % RH, voltage supply 12 VDC
*) Calibration is possible to reduce the zero point error
L-BAL-E292-GB 2023/51 Index 002
*)
Part.-No.
18/21
%
%
%
%
%
% / 10K
% / 10K
% / 10K
% / 10K
zero point calibration
Enclosure
0...1000 Pa
(0...4.0 in.wg)
+/- 0.9
+/- 1.3
0.1
0.6
+/- 1.0
+/- 0.2
+/- 0.4
+/- 0.2
+/- 0.4