Installation and Operating Specification EDR
Information
Alternatively to the automatic zero point calibration, the offset
value can also be set manually see BASE SETUP / Offset.
7.7 Check sensor function
1. Program Mode
2. Connect the voltage supply (+U
0 ...10 V (A / GND).
3. Remove pressure hoses and measure output signal, nominal
= 0 V.
4. Create pressure at the "+" connection against the "-" connec-
tion (e. g. by carefully blowing in), measure the output signal
(0...10 V
5. If the sensor works, reconnect the pressure hoses and check
these if necessary.
L-BAL-E292-GB 2023/51 Index 002
for pressure sensor.