Note:
· Make the function settings shown in Table 1 on M/P-series units as necessary.
· Refer to the Instructions Book when it is necessary to set the settings for CITY MULTI units.
· Table 1 summarizes the setting options for each mode number. Refer to the indoor unit Installation
Manual for the detailed information about initial settings, mode numbers, and setting numbers for the
indoor units.
· Be sure to write down the settings for all functions if any of the initial settings has been changed after the
completion of installation work.
Table1. Function setting options
Mode No.
Mode
01
Automatic recovery after
power failure
02
Thermistor selection
(indoor temperature
detection)
03
LOSSNAY connection
04
Power voltage
05
Auto mode
07
Filter sign
08
Fan speed
09
Outlet
10
Optional parts
(High-efficiency filter)
11
Vane
Settings
Disable
Enable (Four minutes of standby time
is required after the restoration of
power.)
Average temperature reading of the
indoor units in operation
Thermistor on the indoor unit to which
the remote controller is connected
(fixed)
Built-in sensor on the remote controller
Not connected
Connected (without outdoor air intake
by the indoor units )
Connected (with outdoor air intake by
the indoor units )
240 V
220 V, 230 V
Enable (Automatically the unit
achieves effective energy saving
operation.)
Disable
100 hours
2500 hours
Not displayed
Silent mode (or standard)
Standard (or High ceiling 1)
High ceiling (or High ceiling 2)
4 directional
3 directional
2 directional
No
Yes
No vanes (or the vane setting No.3 is
effective.)
Equipped with vanes (The vane
setting No.1 is effective.)
Equipped with vanes (The vane
setting No.2 is effective.)
– 25 –
Setting No.
Unit numbers
1
Set "Grp." for the Unit number.
These settings apply to all the
2
connected indoor units.
1
2
3
1
2
3
1
2
1
2
1
Set "1, 2, 3, 4, or All" for the Unit
number.
2
These settings apply to each indoor
3
unit.
·
1
If "1, 2, 3, or 4" is set for the Unit
2
number, the settings apply only to
the specified indoor unit regardless
3
of the number of connected indoor
1
units (one through four units).
2
·
If "All" is set for the Unit number, the
3
settings apply to all the connected
indoor units regardless of the
1
number of connected indoor units
2
(one through four units).
1
2
3