System response
Accuracy class:
0.2 resp. 0.4 at applications with
phase-shift
Energy meter:
1.0 according to IEC 1036
(0.1 Ir ≤ I ≤ 1.5 Ir)
Duration of the
measurement cycle:
Depending on measured variable
and programming
Response time:
Approx. 1 ... 2 times the measure-
ment cycle and 1...2 s
Infl uencing quantities and permissible variations
Acc. to EN 60 688
Electrical safety
Protection class:
II
Enclosure protection:
IP 40, housing
IP 20, terminals
Overvoltage category:
III
Insulation test:
Input voltage:
Input current:
Output:
Power supply:
Surge test:
5 kV; 1.2/50 μs; 0.5 Ws
Test voltage:
50 Hz, 1 min. according to
EN 61 010-1
5550 V, inputs versus all other circuits
as well as outer surface
3250 V, input circuits versus each
other
3700 V, power supply versus outputs
and SCI as well as outer surface
490 V, outputs and SCI versus each
other and versus outer surface
Power supply
Voltage:
Acc. to type label
AC
AC
AC 207...253 V
AC 360...440 V
AC 450...550 V
AC 623...762 V
DC, AC 24... 60 V
DC, AC 85...230 V
Consumption:
≤ 9 W resp. ≤ 10 VA
32
AC 400 V
AC 400 V
DC 40 V
AC 400 V
DC 230 V
90...110 V
H
= 100 V
n
99...121 V
H
= 110 V
n
H
= 230 V
n
H
= 400 V
n
H
= 500 V
n
H
= 693 V
n
Programming connector on transducer
Interface:
RS 232 C
DSUB socket:
9-pin
5
9
GND
DTR
The interface is electrically insula-
CTS
TXD
RTS
ted from all other circuits.
RXD
DSR
6 1
Installation data
Housing:
Housing T24
Dimensions see section "11. Di-
mensional drawings"
Housing material:
Lexan 940 (polycarbonate),
flammability class V-0 acc. to
UL 94, self-extinguishing, non-
dripping, free of halogen
Mounting:
For snapping onto top-hat rail
(35 × 15 mm oder 35 × 7.5 mm) acc.
to EN 50 022
or
directly onto a wall or panel using
the pull-out screw hole brackets
Mounting position:
Any
Terminals
Type:
Screw terminals with wire guards
Max. wire gauge:
≤ 4,0 mm
2 × 2.5 mm
Ambient conditions
Nominal range of use
for temperature:
0...15...30...45 °C
(usage group II)
Operating temperature: – 10 to + 55 °C
Storage temperature:
– 40 to + 85 °C
Annual mean
relative humidity:
≤ 75%
Altitude:
2000 m max.
Indoor use statement!
2
single wire or
2
fi ne wire