Télécharger Imprimer la page

Madas M14/RMX N.C. Mode D'emploi page 14

Électrovanne a réarmement manuel normalement fermée pour gaz

Publicité

Les langues disponibles

Les langues disponibles

9.0 - RATING PLATE DATA
The user is obliged to keep the marking of the valve clearly visible: any coatings or
paintwork performed on the product that make the valve unidentifiable are not to
be attributed to the manufacturer.
The rating plate data (see example provided here) includes the following:
• Manufacturer's name/logo and address (possible distributor name/logo)
• Mod.:
• CE-51AT1438
• Cl. A
• Gr. 2
• EN 161
• P. max
• PS
• IP....
• 230V....
• TS
(if it is present) = In compliance with PED directive followed by the no. of the Notified Body
• year
• Lot
• U1812
• 7634
• 00001
Protection mode
II
product group
3
product category
Gas: II 3G Ex mc ec nC IIC T... Gc X
G
explosive atmosphere with gas or vapours
Ex
suitable for explosive atmosphere
mc
encapsulated for zone 2
ec
increased safety
nC
sealed device for zone 2
IIC
explosion group
T...
temperature class (T4 < 135 °C) - (T5 < 100 °C) - (T6 < 85 °C)
Gc
Product Level (EPL) - equipment for use in explosive atmospheres due to the presence of gas, with an "increased"
level of protection, which is not a source of ignition during normal operation and which has some additional
protective measures to ensure that it remains an inactive source of ignition in case of events expected regularly
X
particular conditions of use (*)
Dust: II 3D Ex mc tc IIIC T...°C Dc X
D
explosive atmosphere with dust
Ex
suitable for explosive atmosphere
mc
encapsulated for zone 22
tc
protection by enclosure for zone 22
IIIC
explosion group
T...
temperature class expressed in °C
Dc
Product Level (EPL) - equipment for use in explosive atmospheres due to the presence of dust, with an "increased"
level of protection, which is not a source of ignition during normal operation and which has some additional
protective measures to ensure that it remains an inactive source of ignition in case of events expected regularly
X
particular conditions of use (*)
* see paragraph 3.2 - "Special conditions for safe use"
M14/RMX N.C. - M14/RMCX N.C. - M16/RMOX N.C.
= device name/model followed by the connection diameter
= certification pin number
= Seal strength in counterflow at 150 mbar (15 kPa) in accordance with EN 161
= Mechanical resistance group 2 in accordance with EN 161
= Product reference regulation
= Maximum pressure at which product operation is guaranteed
= Allowable maximum pressure
= Protection rating
= Power supply voltage, frequency (if Vac), followed by electrical absorption
= Temperature range within which product operation is guaranteed
= Conformity with Regulation (EU) 2016/426 followed by Notified Body No.
= In compliance with ATEX Dir. followed by the protection mode
(complete protection mode indicated on coil and CPI switch)
= Year of manufacture
= Product serial number (see explanation below)
= Lot issued in year 2018 in the 12th week
= progressive job order number for the indicated year
= progressive number referring to the quantity of the lot
= Disposal in accordance with WEEE directive 2012/19/EU
Mod.:
P.max=PS=6 bar
CE-51AT1438 Cl.A Gr.2 EN 161
230 V/50-60 Hz 9 VA
Year: 2018
14
Madas Technical Manual - 2|2.1aX - REV. 0 of 18
M16/RMOX N.C. DN 25
(600 kPa)
TS: -20+60°C
Lot: U1812
7634/00001
Oct 2023
th

Publicité

loading

Ce manuel est également adapté pour:

M14/rmcx n.c.M16/rmox n.c.