5 Troubleshooting
Code
Display text
H.00.108
Tdhw bottom open
H.02.02
Wait Config Number
H.02.03
Conf Error
H.02.04
Parameter Error
H.02.05
CSU CU mismatch
H.02.16
Int CSU Timeout
H.02.40
Function unavailable
H.02.48
Funct Gr Conf Fault
H.02.55
Inval or miss SerNR
H.02.62
Unsupported function
H.02.63
Unsupported function
H.02.84
Function conflict
H.10.09
T Flow Zone B Open
H.10.10
T Flow Zone B Closed
28
Description
DHW bottom cylinder temperature
sensor is either removed or meas
ures a temperature below range
Waiting For Configuration Number
Configuration Error
Parameter Error
CSU does not match CU type
Internal CSU Timeout
Function unavailable
Function Group Configuration Fault
Invalid or missing device serial num
ber
Zone B doesn't support the selected
function
Zone C doesn't support the selected
function
The current parameters configura
tion is causing a conflict on hard
ware resources
Flow temperature sensor Zone B
Open
Flow temperature sensor Zone B
Closed
Solution
DHW Mixing temperature sensor short-circuited:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
Configuration error or unknown configuration
number:
Reset CN1 and CN2
Configuration error or unknown configuration
number:
Reset CN1 and CN2
Factory settings incorrect:
Parameters are not correct:
Restart the boiler
Reset CN1 and CN2
Replace the CU-GH PCB
Configuration error:
Reset CN1 and CN2
Configuration error:
Reset CN1 and CN2
Replace the PCB
Contact your supplier
SCB not found:
Carry out an auto-detect
Replace the CU-GH PCB
Zone B function setting is not correct or is not al
lowed on this circuit:
Check the setting of parameter CP021.
Zone C function setting is not correct or is not al
lowed on this circuit:
Check the setting of parameter CP023.
Two activated functionalities are using the same
actuators or sensors connector pins:
Verify that no connector pins are shared be
tween activated functionalities
Check if there are no unwanted functionalities
enabled through the parameters
Disable functionalities until the error is resolved
to pinpoint conflicting functionalities
Flow temperature sensor zone B open:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Sensor is not present.
Faulty sensor: replace the sensor
Flow temperature sensor zone B short-circuited:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
7801273 - 1 - 29062022