Parameter
SP119
Hyst temp solar pump
SP052
Tmax recooling mode
SP053
Recooling time delay
SP054
Recooling mode time
SP055
DHW recooling temp
SP057
Tank recool prio
SP089
Max delay solar pump
SP280
Solar tube ON-time
SP099
Solar gradient
SP069
Solar collect start
SP079
Solar collect stop
7801273 - 1 - 29062022
Description
Menu path
Sets the switch delay
temperature between
> Solar Systems > So­
the solar collector tem­
lar Setpoint
perature and either the
DHW temperature or
CH solar tank tempera­
ture before switching
the solar pump to OFF.
Sets the maximum tem­
perature of the solar
> Solar Systems > Re­
collector to be used in
cooling
recooling mode for both
DHW and CH solar
tanks. The recooling
will be stopped if the
solar colector tempera­
ture is below this value
(minus the correspond­
ing offset temperature).
Sets the time delay dur­
ing which the solar col­
> Solar Systems > Re­
lector temperature can
cooling
be below its maximum
(SP052) before the re­
cooling function will be
stopped.
Select the recooling
mode time which must
> Solar Systems > Re­
be used for the DHW
cooling
and CH solar tanks.
Sets the DHW solar cyl­
inder target tempera­
> Solar Systems > Re­
ture when the solar col­
cooling
lector is in recooling
mode.
Select which solar tank
must be recooled first
> Solar Systems > Re­
when the solar collector
cooling
is in recooling mode.
Sets the maximum de­
lay time before forcing
> Solar Systems > Col­
the solar collector pump
lector
to ON if the active solar
tank temperature didn't
reach its maximum al­
lowed value (valid only
for solar collector func­
tion).
Sets the time for the so­
lar pump to be active
> Solar Systems > Col­
for the solar tube col­
lector
lector function.
Sets the maximum gra­
dient for rising solar col­
> Solar Systems > Col­
lector temperature.
lector
Sets the solar collector
function start time. This
> Solar Systems > Col­
is only active when the
lector
Time Mode is selected.
Sets the solar collector
function stop time.
> Solar Systems > Col­
lector
Options
1 40 °C
> Installation Setup
8 90 °C
> Installation Setup
0 60 Min
> Installation Setup
0 240 Min
> Installation Setup
8 90 °C
> Installation Setup
0 CH
> Installation Setup
1 DHW
0 60 Min
> Installation Setup
10 240 Sec
> Installation Setup
0 20 °C/min
> Installation Setup
0 143 HoursMinutes
> Installation Setup
0 143 HoursMinutes
> Installation Setup
en
3 Installation
Factory setting
7
70
40
120
70
0
30
30
1
0
0
17