Parameter
SP031
Tmin solar collector
SP032
Frost protect hyst
SP033
Antifreeze agent %
SP276
Frost protect offset
SP044
Tsetp DHW charge
SP045
Tsetp max DHW
charge
SP046
Tsetp DHW limit
SP109
Toffset solar pump
SP281
Hyst recooling temp
16
Description
Menu path
Sets the minimum al­
lowed temperature in
> Solar Systems > Pro­
the solar collector to
tection
prevent the heat con­
ducting medium from
freezing. The value de­
pends on the antifreeze
agent concentration.
Sets the frost protection
hysteresis temperature.
> Solar Systems > Pro­
This value is added to
tection
or distracted from the
offset temperature to
respectively start or
stop the frost protection
function.
Sets the amount of anti­
freeze agent (ex­
> Solar Systems > Pro­
pressed as a percent­
tection
age) that is added to
the heat conducting
medium.
Enable (1) or disable
(0) the calculation for
> Solar Systems > Pro­
the frost protection off­
tection
set temperature with re­
spect to the antifreeze
agent concentration.
Sets the nominal set­
point temperature to
> Solar Systems > So­
charge the DHW cylin­
lar Setpoint
der with solar energy.
Sets the maximum set­
point temperature to
> Solar Systems > So­
charge the DHW cylin­
lar Setpoint
der with solar energy. If
the temperature in the
DHW cylinder is lower
than this value, the
DHW cylinder will be
used for storing heat.
Sets the setpoint for the
DHW cylinder limit tem­
> Solar Systems > So­
perature. If this temper­
lar Setpoint
ature is reached, the
charging of the DHW
cylinder will be stopped.
Sets an offset tempera­
ture between the solar
> Solar Systems > So­
collector temperature
lar Setpoint
and either DHW or CH
solar tank temperature
before switching the so­
lar pump to ON.
Sets the hysteresis
(switch delay) tempera­
> Solar Systems > So­
ture for the recooling
lar Setpoint
mode. This value is
added to the maximum
recooling temperature
to stop the recooling
mode.
Options
-20 5 °C
> Installation Setup
5 40 °C
> Installation Setup
0 60 %
> Installation Setup
0 Inactive
> Installation Setup
1 Active
8 60 °C
> Installation Setup
8 90 °C
> Installation Setup
40 95 °C
> Installation Setup
1 40 °C
> Installation Setup
0 20 °C
> Installation Setup
Factory setting
0
5
0
1
60
80
75 °C
3
0
7801273 - 1 - 29062022