Code
Display text
H.00.69
TbufferTankOpen
H.00.70
TbufferTankClosed
H.00.71
TbufferTankTopOpen
H.00.72
TbufferTankTopClosed
H.00.74
TBufferTankMissing
H.00.75
TBufferTankTop Miss
H.00.105
Tdhw circ open
H.00.106
Tdhw circ closed
H.00.107
Tdhw bottom closed
7801273 - 1 - 29062022
Description
Buffer Tank temperature sensor is
either removed or measures a tem­
perature below range
Buffer Tank temperature sensor is
either shorted or measures a tem­
perature above range
Buffer Tank top temperature sensor
is either removed or measures a
temperature below range
Buffer Tank top temperature sensor
is either shorted or measures a tem­
perature above range
Buffer Tank temperature sensor was
expected but not detected
Buffer Tank Top temperature sensor
was expected but not detected
DHW circulation temperature sensor
is either removed or measures a
temperature below range
DHW circulation temperature sensor
is either shorted or measures a tem­
perature above range
DHW bottom cylinder temperature
sensor is either shorted or measures
a temperature above range
Solution
Buffer tank temperature sensor open:
Bad connection: check the wiring and connec­
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Sensor is not present.
Faulty sensor: replace the sensor
Buffer tank temperature sensor short-circuited:
Bad connection: check the wiring and connec­
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
Buffer tank top temperature sensor open:
Bad connection: check the wiring and connec­
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Sensor is not present.
Faulty sensor: replace the sensor
Buffer tank top temperature sensor short-circuit­
ed:
Bad connection: check the wiring and connec­
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
Buffer tank temperature sensor not detected:
Buffer tank temperature sensor is not connec­
ted: Connect the sensor
Buffer tank temperature sensor is not connec­
ted correctly: Connect the sensor correctly
Faulty sensor: replace the sensor
Buffer tank top temperature sensor not detected:
Buffer tank top temperature sensor is not con­
nected: Connect the sensor
Buffer tank top temperature sensor is not con­
nected correctly: Connect the sensor correctly
DHW circulation temperature open:
Sensor is not present.
Bad connection: check the wiring and connec­
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
DHW circulation temperature sensor short-circuit­
ed:
Bad connection: check the wiring and connec­
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
DHW Mixing temperature sensor open:
Sensor is not present.
Bad connection: check the wiring and connec­
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.