REFERENCE DRAWING – INSTALLATION OF PHOTOCELLS
INTERLOCK FUNCTION (from version 5V4)
System based on the presence of two doors, in which the "open" state of one door disables the
opening of the other one.
The diagram shows a connection between two boards that control two automatic doors on "IN-
TERLOCK" configuration
J17
J16
27
26
25
24
23
22
21
20
19
18
-
28
B
29
J2
A
30
LED-13
LED-12
LED-11 LED-10
LED-9 LED-8 LED-7 LED-6 LED-5
+
31
1_Connect terminal 21 of the control board "A" to terminal 6 of the control board "B".
2_Terminal 21 of the control board "B" must be connected to terminal 6 of the control board "A"
3_Connect the GND of both control boards.
4_In order to enable the INTERLOCK function, put DIP 9 in ON on both control boards.
5_Decide which boad must open first in case of simultaneous opening. Put DIP 10 in OFF on the
control board with HIGH priority. Put DIP 10 in ON on the control board with LOW priority.
With DIP9 in ON, the entry of terminal 23 (Stop/No panic) changes use. By
connecting a switch between 23 and 20, it is possible to DISABLE the interlock
function.
LEARNING
WARNING: During programming there must be no obstacles in the door's area or within sen-
sor's detection range, otherwise programming will fail and must be repeated.
The door can't be "helped" manually and the trimmers cannot be changed.
In case one of the following parameters are changed, programming must be repeated: door
leaves' travel, door leaves' weight, opening direction, (see DIP # 4 on SW2).
Press without releasing button P1 on the board. LED DL1 will start flashing yellow, and at the same
time the door will start opening and closing slowly to find the limit switches. At the end the door
will open and close at normal speed.
TX1
RX2
J8
J4
J10
17
16
15
14
13
12
11
10
9
8
7
6
5
A
RX1
TX2
J17
J7
J9
J13
J5
4
27
26
25
24
-
28
B
29
J2
A
30
LED-13
LED-12
LED-11 LED-10
J11
+
31
25
J16
J8
F 5 - 3,15 A
23
22
21
20
3
19
18
2
17
16
1
15
14
13
12
11
10
IN 230Vac
J14
IN 230Vac
LED-9 LED-8 LED-7 LED-6 LED-5
J4
J10
9
8
7
6
5
4
B