Power:
Operating temperature: -20ºC to 50ºC (-4ºF to 122ºF)
Operating humidity:
Sensor type:
Visual indicator:
Size (DxWxH):
Weight:
Detection Ranges and Alarm Levels
Gas Detected
CO
Carbon monoxide 0-250 ppm
H
S
Hydrogen sulfide 0-50 ppm
2
NO
Nitrogen dioxide
2
O
Oxygen
2
COMB Combustibles
Maximum Overload is the cell exposure to gas concentration that may
result in permanent damage to the cell.
Sensor Overload
Sensor overload occurs whenever the gas concentration reading
is higher than the full scale value, no matter how high the gas
concentration is.
Overload Warning state is latched when true. It stays activated
indefinitely and independent of gas concentration reading.
3
E
Point Remote Gas Sensor User Manual
Specifications
Electrochemical sensor: 10-24 VDC, 50 mA
Catalytic: 10-16 VDC, 100 mA
15 to 90% relative humidity (non-condensing)
Electrochemical cell (CO, NO
(Comb)
Amber LED (Tx)
3.5 x 4.5 x 6.5 cm (1.36 x 1.75 x 2.56 in.)
38 g (1.34 oz.)
Range
Alarm A Alarm B Alarm C
25 ppm
10 ppm
0-10 ppm
0.7 ppm
0-25 %vol
19.5 %vol. 22 %vol. 23 %vol
0-100 %LEL
25 %LEL
, H
S, O
); catalytic
2
2
2
200 ppm 225 ppm 500 ppm
15 ppm
45 ppm
2 ppm
5 ppm
50 %LEL 90 %LEL 100 %LEL
Maximum
Overload
150 ppm
1000 ppm
100 %vol
7