Pentair INTELLIBOOST MIB0715B Manuel D'utilisation page 8

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

discharge. See "Electrical Safety" and
"Electrical Connection".
Risk of flooding. Close
system shut-off valves before removing
any plugs, caps, or fittings from the
pump. System water pressure will
prevent replacing the fittings once they
are removed.
In normal conditions, electric pumps do
not require any scheduled maintenance.
Periodically check the pressure delivered
and current draw. Reduced pressure
indicates pump wear. Increased current
draw indicates abnormal mechanical
friction in the pump.
Special maintenance may be required
to clean the pump and replace any worn
parts.
At least twice a year, inspect the
expansion tank and check the pre-
charge pressure, the sealing efficiency
of the joints, and all areas for visible
signs of damage and/or corrosion. To
check the pre-charge pressure, close
the shut-off valves on both sides of the
pump, turn off the pump, and drain all
water from the variable speed booster
system until the system water pressure
has returned to zero. On completion of
the check, restore the system to normal
conditions.
If the pump is not used for prolonged
periods (e.g. for an entire season) drain
it completely, rinse it with clean water,
and store it in a dry location.
SIGNALS, ALARMS STATUS
AND ERRORS
Programming
1. Language setting:
To change the language, press the SET
button (see Figure 5).
LINE
60 PSI
PRESSURE
RUN
FAULT
MODE
Figure 5
2. Display setting.
Press MODE to change the display
configuration and choose between
GRAPHIC (a) and TEXT (b) modes (see
Figure 6).
a)
LINE
RUN
MODE
b)
Figure 6
3. Pressure level setting (set-point)
To increase or decrease the set-point,
press the up
(See Figures 7 and 8).
8
PRESSION
fr
en
PRESSURE
es
PRESIÓN
SET
ESC
LINE
RUN
FAULT
MODE
SET
ESC
LINE
60 PSI
RUN
FAULT
MODE
or down
buttons

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Intelliboost mib0715s

Table des Matières