Installation of Electric Auxiliary Heat Module
(for some models)(not supplied)
Accessories
Name
Owner's and Installation
manual
Seal sponge
Screw
Rubber cap
Electric auxiliary heating
wiring diagram
Air switch label
NOTE
Installation must be performed by an
authorized dealer or specialist. Please
make necessary protection when
installing the unit.
Specification series of electric auxiliary heat module:
3kW,5kW,8kW,10kW, 15kw, 20kW,25kW.
If the unit needs to be equipped with electric
auxiliary heat module, please check the electric
auxiliary heat module specification that can be
matched with the unit first to avoid unnecessary
consequences caused by improper matching.
Selection and matching of internal machine and
electric auxiliary heating components
MODEL
3kW
5kW
8kW
(Btu/h)
12K
Y
Y
Y
18K
Y
Y
Y
24K
-
Y
Y
30K
-
Y
Y
36K
-
Y
Y
48K
-
-
Y
60K
-
-
-
Shape
Quantity
1
1
7
1
1
1
10kW
15kW
20kW
25kW
-
-
-
-
Y
-
-
-
Y
Y
-
-
Y
Y
-
-
Y
Y
Y
-
Y
Y
Y
-
Y
Y
Y
Y
Page 26
NOTE
Use only modules that are compatible and
certified for use with the model. Please refer
to the electric auxiliary heater model
specifications for additional details to ensure
proper selection and installation.
Installation Requirements
Before installation, please check the list of electric
auxiliary heat modules and physical objects. After
transportation, check whether the electric heating
is damaged. If any damage is found, please contact
the after-sales personnel immediately.
Electric Auxiliary Heat Module
Installation and Wiring Operation
1. Remove the upper cover and use professional
tools to remove the knock-out holes of the
upper cover.