Address DIP switch:
Address dialing S1+S2: When a centralized
controller is used, address dialing is required.
Network address: The address silkscreen is a NET
address, consisting of a 16-bit rotary address
code S2 and a two-digit DIP switch S1 (set
during technical installation, no network
function needs to be set).
When S2 is 00 (the dialing code is not
connected), the value of the network address is
the value of S2; when S2 is 10 (corresponding to
the hardware switch connected to a 10K
resistor), the value of the network address is S2
plus 32.
When S2 is 01 (corresponding to the dialing
code of the 5.1K resistor connected to the
hardware activated), the value of the network
address is the value of S2 plus 16.
When S2 is equal to 11 (all dialing codes are
activated), the value of the network address is
the value of S2 plus 48.
Determined by dial code S2 1-10K 2-5.1K
Dial code selection
Network address
ON
1 2
ON
1 2
ON
1 2
ON
1 2
S2 + 48
S2 + 32
S2 + 16
S2
Page 4 9
Static pressure DIP switch:
SW4
The code is only valid for 1-3. The composition
of the binary code corresponds to a different
static pressure of the wind profile.
000 is the default value;
000/001/010/011/100/101/110/ 111, with
different capacities of the indoor unit, electric
heater and PSC for selection and use,
corresponding to different air volumes. See air
volume table for further details.