Emergency stop in the housing M12
General data
Rated voltage
Rated current
Operating temperature
Storage temperature
Protection rating
Connection
Electrical life cycle
Mechanical life
Continuity resistor (new)
Bounce time
Direct opening action (contactors)
Forced opening travel
B
10D
Short-circuit protective device
Pollution degree
Electrical data: M12 connector
Rated voltage
Rated current
Impulse Test Voltage
Electrical data: Contactors, acc. to IEC/EN 60947-5-1
Utility category
Rated operating voltage Ue
(Rated operation current Ie)
Switching cycles
Thermal continuous current Ith
Rated short-circuit current
Electrical data: Contactors, acc. to IEC/EN 61058-1
Rated voltage Ue
Rated current Ie
Doc. # BA000612 – 05/2023 (Rev. E)
SNH 2402 M12
Max. 60 V
Max. 4 A (40 °C)
-25 °C ... +60 °C
-25 °C ... +85 °C
IP65 (with a connected M12 connector)
M12 connector (m), 5-pin
Pin 5,2: Opener 1; Pin 1,4: Opener 2; Pin 3: n.c.
50,000 at nominal load (contactors)
50,000 switching cycles (Ambient temperature =
20 °C)
< 30 mΩ
< 9 ms
According to EN 60947-5-1, Appendix K
> 3mm
250,000
Fuse cutout 4A gG
3
Max. 60 V
Max. 4 A (40 °C)
1.5 kV
AC15
250 V (3 A)
10Ie
16A
1000 A
250 V~
16 (10) A
SNH
DC13
250 V (0,2 A), 125 V (0,4 A)
60 V (1 A), 24 V (2 A)
1.1Ie
EN 28 / 99