ENGLISH
Wood consumption
The efficiency of Jøtul I 400 gives it a nominal heat output of 6.0 kW.
Wood consumption, at nominal heat output: Approx. 1.9 kg/h.
The size of the pieces of wood should be:
Kindling (finely split wood):
Length: approx. 20-30 cm
Diameter: 2-5 cm
Quantity required each time: 6 - 8 pieces
Wood (split wood):
Recommended length: 30 cm
Diameter: Approx. 8 cm
Interval for adding wood: Approx. every 50 minutes
Fire size: 1.6 kg (nominal output)
Quantity required each time: 3 pieces
Nominal heat output is achieved when the air vent is open
approx. 40 % (fig. 4 A).
20
3.0 Installation
3.1 Floor
Foundations
You need to make sure the foundation is suitable for a stove. See
"2.0 Technical data" for specified weight.
Requirements for protection of wooden
flooring beneath the stove
Jøtul I 400 has a heat shield underneath to protect the floor from
radiated heat. The product can therefore be positioned directly
on a wooden floor that has been covered by a sheet of metal
or other non-inflammable material. Recommended thickness
minimum 0.9 mm and must cover the entire floor surface within
the surround.
It is recommended that flooring that is not attached to the
actual floor surface – "floating floors" – be removed beneath
the installation.
Any floor covering of inflammable material, such as linoleum,
carpets, etc. must be removed from under the floor plate.
Requirements for protection of inflammable
floors in front of the stove
The floor in front of the stove must be protected by a sheet
of metal or other non-inflammable material. Recommended
thickness is minimum 0.9 mm.
The front plate must comply with national laws and
regulations.
Contact your local building authorities regarding restrictions and
installation requirements.
3.2 Wall
Distance to inflammable wall protected by
insulation (fig. 1)
Insulation requirements50 mm rock wool 120 kg/m
aluminium foil on one side.
Distance to inflammable wall protected by
firewall (fig. 1)
Requirements for regulation firewalls
The firewall must be a minimum of 100 mm thick and be made
of brick, concrete or lightweight concrete. Other materials and
structures with satisfactory documentation may also be used.
Contact your local building authorities regarding restrictions and
installation requirements.
Distance to non-inflammable wall (fig. 1)
"Non-inflammable wall" here means a non-bearing wall of
continuous brickwork/concrete.
3
with