UM_s-MEXT_ME18relC_00_11_18_ML
Icon
TIME BANDS ACTIVATED
FREE COOLING ACTIVATED
DELIVERY AIR TEMP.
PROTECTION ACTIVATED
DEHUMIDIFY PROTECTION
ACTIVATED
SAFETY REDUCTION LOAD
(LP) ACTIVATED
POST-VENTILATION
ACTIVATED
DELAY FOR TIME
OBSERVATION
HIGH TEMPERATURE pLAN
RESCUE ACTIVATED
LOW TEMPERATURE pLAN
RESCUE ACTIVATED
HIGH HUMIDITY pLAN
RESCUE ACTIVATED
LOW HUMIDITY pLAN
RESCUE ACTIVATED
HOT SPOT PROTECTION
ACTIVATED
COLD SPOT PROTECTION
ACTIVATED
ACTIVE FAN ON STAND-BY
ACTIVATED
PERIODIC CHECK
Note: All the active functions of the unit are displayed (with flashing of various icons).
USER MANUAL
Function
Meaning
Time bands active
Time bands active
Free cooling active
Unit in free-cooling mode
Delivery air temperature
The application is limiting cooling demand to avoid excessively cold delivery air
protection active
Dehumidification protection
The dehumidification protection is active (maximum or minimum temperature)
active
The Safety Reduction Load LP (low pressure) function is enabled. The internal
Safety Reduction Load LP
fan of the unit and the inverter are controlled to prevent excessively low pressure
in the low pressure section.
Post-ventilation active
The heater cooling post-ventilation is active
One or more compressors are blocked to comply with the start-up times, or the
Delay for time obs.
unit is awaiting regulation
High temperature pLAN
The pLAN network logics activate the unit when the high temperature limit is
rescue active
exceeded.
Low temperature pLAN
The pLAN network logics activate the unit when the low temperature limit is
rescue active
exceeded.
High humidity pLAN rescue
The pLAN network logics activate the unit when the high humidity limit is
active
exceeded.
Low humidity pLAN rescue
The pLAN network logics activate the unit when the low humidity limit is
active
exceeded.
Hot Spot protection for a
The unit considers its local temperature instead of the average temperature to
pLAN network
control the Hot Spot concerned.
Cold Spot protection for a
The unit considers its local temperature instead of the average temperature to
pLAN network
control the Cold Spot concerned.
Active Fan on Standby
The unit is on standby but the fan continues to run at a set speed
The unit forces the cooling demand sent to the PAC-IF cards to minimum and
Periodic override
keeps ventilation at maximum to help prevent the formation of ice on the piping.
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
40