2. Usage conditions/environment
2-1. Usage conditions
Usage
Refrigerant type
Evaporation temperature
Suction pressure
Heat level of suction gas
Suction gas temperature
Discharge pressure
Discharge gas temperature
Compressor shell bottom
temperature
Outside air temperature
Power supply voltage
Voltage imbalance
Connected pipe length
(suction/liquid)
Installation location
*1
Length that meets the piping work conditions stated in the Installation Manual, guarantees the proper oil return to
the unit, and prevents refrigerant overcharge.
*2
Indicates an equivalent length.
*3
Refer to the relevant pages for details about the connected pipe length and allowable amount of refrigerant to be
charged.
*4
Refer to the relevant pages. (Page 19)
2-2. Usage conditions/environment
Follow the condition/environment specified below for installation.
Do not install the unit on moving vehicles such as cars
or ships.
Do not install the unit in a place where acidic solutions
or sprays containing sulfur are used frequently.
Avoid unsuitable places (hot springs, places where
chemicals are frequently used) for installation.
Install the unit in an area where the noise from the unit
will not disturb the neighbors.
Do not install the unit in a place where it is subjected to
radiant heat from other heat sources.
Properly install the unit on a stable, load-bearing sur-
face.
Do not install the unit in any environment where it can
be exposed to airborne iron or copper powder, acidic or
alkaline atmosphere, or an accumulation of a large
amount of sand containing sea salt particles. Such en-
vironments can cause corrosion of the aluminum pipes.
WT09614X03_GB
-
-
°C
MPa
K
°C
MPa
°C
°C
°C
-
3-phase 4-wire 380/400/415 V ± 10%, 50 Hz
%
m
-
14
Low/Medium temperature
R744
-35 to -5
1.10 to 2.94
10 to 40
18 or below
2.75 to 11.0
120 or below
80 or below
-25 to 43
2 or less
*1*2*3
50 or below
*4
Outdoor
Do not install the unit in a place where large amount of
oil, steam, ammonia, or corrosive gas such as sulfuric
gas is present. (Such place includes near a chimney
opening.)
Do not install the unit in a space that is not large enough
as specified in the Installation Manual. (Page 20)
Do not install the unit in an area with heavy snowfall ex-
ceeding the tolerance of snow prevention work advised
in this manual. (Page 21)
Do not install the unit in an area where the air is stag-
nant, such as indoors, in a halfway basement, or in a de-
pressed space.