10-3. Electrical characteristics
Model
Power source
Electrical
Electric power consumption
characteris-
Running current (380V/400V/415V) <Note 1>
tics
Starting current
Maximum current
Compressor
Rotation per minute (RPM)
Electric heater <oil>
Condenser
Fan
Electrical wir-
Electric wire size
ing
Overcurrent protector
Switch capacity
Control circuit wire size
Grounding wire diameter
Phase advance capacitor
(Compressor)
<Note 6>
Note 1 Measurement conditions are as follows.
Outside air temperature: 32°C, evaporation temperature: -10°C, suction superheat: 10 K
Inverter compressor operating frequency: 66 Hz (ECOV-X37VA), 95 Hz (ECOV-X55VA)
Note 2 The figures in the angle brackets in the "Electric wire size" row indicate the maximum wire length where the voltage drop is 2 V
or less.
Note 3
Specific wiring requirements should adhere to the wiring regulations of the region.
Power supply cords of appliances shall not be lighter than polychloroprene sheathed flexible cord (design 60245
Note 4
IEC57).
Note 5 An earth leakage breaker with at least 3 mm contact separation in each pole shall be provided by the installer.
Leaked current varies depending on wire length, wire routing, and/or presence of devices that emit high frequency.
Select high-harmonic-type earth leakage breakers.
Note 6 Do not use a phase-advancing capacitor with inverter compressor.
®
If MODBUS
is used, follow the instructions below.
• Do not connect a power supply to the terminal block for transmission lines. If connected, the electronic parts will burn out.
• Use shielded cables for transmission wiring.
Wiring using a multi-core cable with different types of transmission wires compromises correct transmission of signals and
results in a malfunction.
• When splicing transmission wires, make sure to splice the shielded cables as well.
For details, refer to section 10-6.
WT09614X03_GB
3-phase 4-wire, 380 to 415 V, 50 Hz
<Note 1>
kW
A
A
A
-1
min
W
Motor output
W
2
<Note 2>
mm
Local switch
A
Branch
A
switch
Local switch
A
Branch
A
switch
2
mm
2
mm
Capacity
μF
kVA
2
Wire size
mm
42
ECOV-X37VA
3-phase 4-wire, 380 to 415 V, 50 Hz
6.25
10.8/10.3/9.93
8
20
61
45
74 x 2
5.5 or larger
25
25
25
25
1.6 or larger
3.5 or larger
N/A
N/A
N/A
ECOV-X55VA
10.0
17.3/16.5/15.9
8
20
95
45
74 x 2
5.5 or larger
25
25
25
25
1.6 or larger
3.5 or larger
N/A
N/A
N/A