Télécharger Imprimer la page

Sime ATLANTIS HM ErP Serie Mode D'emploi page 51

Masquer les pouces Voir aussi pour ATLANTIS HM ErP Serie:

Publicité

Les langues disponibles

Les langues disponibles

TABELLA DELLE VARIABILI MODBUS / MODBUS BOILER VARIABLES LIST
Variable description
Digital variables (COILS)
1
Boiler CH Enable/Request
2
Boiler DHW Enable
3
Boiler Water Filling Function
32
Boiler CH Mode
33
Boiler DHW Mode
34
Boiler Flame Status
35
Boiler Alarm Status
1
Boiler CH Primary Setpoint
2
Boiler DHW Primary Setpoint
3
Boiler DHW Setpoint
4
Outside Temperature MB
5
Boiler CH Curve Slope
6
Boiler CH Curve Displacement
7
Boiler Delta-T CH
64
Boiler DHW Water Temperature
65
Boiler Primary Water Temperature
66
Boiler Return Water Temperature
67
Boiler Flue Gas Temperature
68
Boiler Relative Modulation Level
69
Boiler Primary Water Pressure
70
Boiler Outside Temperature
129
Boiler Current Minute
130
Boiler Current Hour
131
Boiler Current Day of the Week
132
Boiler Current Day of the Month
133
Boiler Current Month
134
Boiler Current Year
192
Boiler Alarm Code
193
Boiler Slave 1 Alarm Code
194
Boiler Slave 2 Alarm Code
195
Boiler Slave 3 Alarm Code
196
Boiler Slave 4 Alarm Code
197
Boiler Slave 5 Alarm Code
198
Boiler Slave 6 Alarm Code
199
Boiler Slave 7 Alarm Code
200 Boiler Combustion Parameter (Par1)
201
Boiler Hydraulic Parameter (Par2)
COMANDI MODBUS SUPPORTATI / MODBUS COMMANDS SUPPORTED
Code
01
15
03
16
05 (partially supported)
04 (partially supported)
06 (partially supported)
D R/W
-
0
1
D R/W
-
0
1
D R/W
-
0
1
D
R
-
0
1
D
R
-
0
1
D
R
-
0
1
D
R
-
0
1
A
0,1°C
20,0
80,0
R/W
equivale a nessun valore ricevuto e viene
mantenuta la termoregolazione di caldaia
A
0,1°C
20,0
80,0
R/W
Se viene ricevuto un valore fuori range equivale
A
0,1°C
10,0
80,0
R/W
Valore di temperatura esterna comunicato via ModBus.
Se viene ricevuto un valore fuori range equivale
A
0,1°C
-55,0
95,0
R/W
a nessun valore ricevuto. Nel caso di conflitto
(utilizzato al posto della curva impostata in caldaia).
A
0,1
3,0
40,0
R/W
Se viene ricevuto un valore fuori range equivale
(utilizzato al posto dello shift impostato in caldaia).
A
0,1
-5,0
5,0
R/W
Se viene ricevuto un valore fuori range equivale
A
0,1
10,0
40,0
R/W
Valore di setpoint Delta-T (Mandata - Ritorno) Value setpoint Delta-T (Delivery - Return)
A
R
0,1°C
0,0
100,0
A
R
0,1°C
0,0
100,0
Temperatura Sonda Circuito Primario (Mandata)
A
R
0,1°C
0,0
100,0
Temp. Sonda Ritorno Circuito Primario (NO cascata)
A
R
0,1°C
0,0
200,0
Livello Modulazione (0%=Minima Potenza -
A
R
0,1%
0,0
100,0
A
R 0,1 bar
0,0
6,0
A
R
0,1°C -100,0
100,0
dalla caldaia tramite la sonda ad essa collegata.
I
-
0
59
R/W
I
-
0
23
R/W
I
-
1 = Lun 7 = Dom
R/W
I
-
1
31
R/W
I
-
1
12
R/W
I
-
2000
2200
R/W
I
R
-
0
100
anomalia caldaia (Master se in cascata).
Codice numerico visualizzato durante
I
R
-
0
100
anomalia caldaia slave 1 (Solo cascata)
Codice numerico visualizzato durante
I
R
-
0
100
anomalia caldaia slave 2 (Solo cascata)
Codice numerico visualizzato durante
I
R
-
0
100
anomalia caldaia slave 3 (Solo cascata)
Codice numerico visualizzato durante
I
R
-
0
100
anomalia caldaia slave 4 (Solo cascata)
Codice numerico visualizzato durante
I
R
-
0
100
anomalia caldaia slave 5 (Solo cascata)
I
R
-
0
100
anomalia caldaia slave 6 (Solo cascata)
I
R
-
0
100
I
R
-
0
199
Valore del PAR 1 in caldaia (Master se in cascata)
I
R
-
0
199
Valore del PAR 2 in caldaia (Master se in cascata)
Descrizione /
Function
Richiesta riscaldamento zona 1
Request CH zone 1
Abilitazione preparazione ACS
Enable DHW preparation
Not used
Non usato
State CH zone 1
Stato riscaldamento zona 1
Stato preparazione ACS
State preparation DHW
Stato presenza fiamma
State presence flame
State presence alarm
Stato presenza allarme
Setpoint CH zone 1.
Setpoint riscaldamento zona 1.
Se viene ricevuto un valore fuori range
If you receive a value out of range
so the value isn't received and
the boiler temperature control is
a punto fisso o a curva climatica.
maintained of fixed point or a
temperature curve.
Setpoint circuito primario durante
Setpoint CH during ACS preparation
la preparazione ACS
(for PAR 66 installer parameters)
(al posto di PAR 66 caldaia).
If you receive a value out of range
the value isn't received and it is used
a nessun valore ricevuto e viene utilizzato
the boiler value regulation .
il valore di regolazione presente in caldaia.
Setpoint acqua calda sanitaria.
Setpoint ACS.
Se viene ricevuto un valore fuori range
If you receive a value out of range
equivale a nessun valore ricevuto
the value isn't received and it is used
e viene utilizzato il valore
the boiler value regulation.
di regolazione presente in caldaia.
External value of temperature by MobBus.
If you receive a value out of range
the value isn't received. In case of
la caldaia dà la priorità al valore della sonda
conflict the boiler will give priority to the value
ad essa collegata.
of the probe connected to it.
Pendenza della curva climatica della zona 1
Slope of heating curve of zone 1
(it is used instead of the curve set in the boiler).
If you receive a value out of range
a nessun valore ricevuto e viene utilizzata
the value isn't received and it is used
la curva climatica presente in caldaia.
the boiler heating curve.
Shift value of room zone 1 set
Valore di shift del set ambiente della zona 1
(it is used instead of the shift set in the boiler).
If you receive a value out of range
a nessun valore ricevuto e viene utilizzato
the value isn't received and it is used
lo shift presente in caldaia.
the boiler heating curve.
Temperatura Sonda Acqua calda sanitaria
DHW temperature sensor
CH temperature sensor (Delivery)
CH temperature sensor (Return) (No cascade)
Smoke temperature sensor (No cascade)
Temperatura Sonda Fumi (NO cascata)
Modulation level: (0%= minimum power
100%= maximum power)
100%=Massima Potenza)
Pressure value water CH
Valore Pressione Acqua Circuito Primario
Valore di temperatura esterna letto
Outside temperature read from the boiler
through the probe connected to it
Non usato
Not used
Non usato
Not used
Non usato
Not used
Non usato
Not used
Non usato
Not used
Non usato
Not used
Codice numerico visualizzato durante
Numeric code shown during boiler error
(If Master is in cascade)
Numeric code shown during slave 01 error
(Only cascade)
Numeric code shown during slave 02 error
(Only cascade)
Numeric code shown during slave 03 error
(Only cascade)
Numeric code shown during slave 04 error
(Only cascade)
Numeric code shown during slave 05 error
(Only cascade)
Codice numerico visualizzato durante
Numeric code shown during slave 06 error
(Only cascade)
Codice numerico visualizzato durante
Numeric code shown during slave 07 error
anomalia caldaia slave 7 (Solo cascata)
(Only cascade)
PAR 1 value (If Master is in cascade)
PAR 2 value (If Master is in cascade)
Name
READ COIL STATUS
WRITE MULTIPLE COILS
READ HOLDING REGISTERS
WRITE MULTIPLE REGISTERS
WRITE SINGLE COIL
READ INPUT REGISTER
WRITE SINGLE REGISTER
FR
NL
DE
51

Publicité

loading