11 Technical Data
GENERAL DATA
Max. voltage (V
)
N
Max. input short-circuit current (IscSTC)
Max. output short-circuit current (IscSTC)
MECHANICAL DATA
Enclosure
Enclosure Dimensions (W x D x H in mm)
Weight
Degree of Protection
Protection Class
Color (RAL)
ENVIRONMENT DATA
Ambient temperature during normal operation
Ambient temperature during storage
Humidity
Altitude
DC INPUT DATA
Number of strings
Sealing range cable entry
Input cable glands entry (per pole)
Input connection
Conductor cross-section
Fuse holder
Fuse type
Max. fuse size
DC OUTPUT DATA
Output cable glands
Clamping Area
Conductor Material
Terminal Type
Switch Type
SPD Protection
SPD Iscpv
(Note 1) Derating of V
versus altitude. 1.0 % per 100 m from 2,001 m to 3,000 m.
N
(Note 2) For Aluminum cable use the correct cable lug.
Installation Manual
DC-CMB-U15-8
GRP (Glass Fiber Reinforced Polyester)
24 kg
IP 54 (outdoor installation)
0 % to 95 % non-condensing
8
8 PG32 with 2 input
each
DIN Rail Mounting - 1 pole - 1,500 V
22 x 65 - 1,500 V
Nr. 1 M50x1.5 (with reduction) per pole
Copper or aluminium ( Note 2)
Cable lug on Copper bus-bar with M12 screw
Under Load Switch-Disconnector - 3 pole - 1,500 V
SPD Type II 15 kA/40 kA
DC-CMB-U15-9
DC 1,500 V (Note 1)
27.5 A
300 A
550 x 270 x 650
25 kg
CLASS II
RAL 7035
-25°C to 50°C
-25°C to 70°C
up to 3,000 m
9
8 mm to 10 mm
10 PG32 with 2 input
each
Directly on Fuse Holder
10 mm
2
- gPV
DC
50 A
17 mm to 38 mm
6,000 A
DC-CMB-IA-U15-xx-en
11 Technical Data
DC-CMB-U15-10
25 kg
10
10 PG32 with 2 input
each
DC
DC
33