Télécharger Imprimer la page

Dimplex LA 1728 Instructions D'installation Et D'utilisation page 21

Publicité

Les langues disponibles

Les langues disponibles

LA 1728
Once the heat pump has been set up in its intended location,
the transport fastenings (2x M6 screws) must be removed from
the compressor plate (the front or rear panel at the bottom
must be removed for this)
transport lock
CAUTION!
Before commissioning, the transport fastening must be
removed.
www.glendimplex.de
5
Installation
5.1 General
The device should always be installed on a permanently
smooth, even and horizontal surface. The entire frame should
be in direct contact with the ground in order to ensure an ade-
quate soundproof seal, to prevent the water-bearing compo-
nents from becoming too cold and to protect the inside of the
device from small animals. If this is not the case, additional insu-
lation measures may be necessary. To prevent small animals
from entering the inside of the device, the connection hole in
the base plate must be sealed, for example. Furthermore, the
heat pump should be set up so that the air outlet direction of
the fan is perpendicular to the main wind direction to allow un-
restricted defrosting of the evaporator. The heat pump is de-
signed for installation on even ground. In the case of different
conditions (e.g.: installation on a platform or flat roof) or there is
a greater risk of the heat pump tipping over (due to an exposed
position or high wind exposure), additional protection against
tipping over must be provided. The responsibility for the heat
pump installation lies with the specialist system construction
company. During the installation, local requirements such as
building regulations, static load of the building, and wind expo-
sure must be accounted for.
It must be possible to carry out maintenance work without hin-
drance. This is ensured when observing the distances to solid
walls as shown in the figure.
0,5 m
CAUTION!
Do not restrict or block the area around the air intake or outlet.
CAUTION!
Observe country-specific building regulations!
CAUTION!
The physical impacts must be observed for installation close
to walls. No windows or doors should be present in the area
surrounding the air outlet of the fan.
CAUTION!
In cases of installation close to a wall, there may be more
sediment in the air inlet and outlet areas due to the air current.
The colder outside air outlet should discharge in such a way as
to not increase the heat losses in heated neighbouring rooms.
452166.66.44a · FD 0207
0,5 m
2 m
0,5m
English
EN-5

Publicité

loading