Installation
2.5
Scope of delivery
Key to Fig. 1:
[1]
Outdoor unit (filled with refrigerant)
[2]
Indoor unit (filled with nitrogen)
[3]
Cold catalyst filter (black) and bio filter (green)
[4]
Drainage elbow with gasket (for outdoor unit with floor or wall
mounting bracket)
[5]
Remote control
[6]
Remote control holder with fixing screw
[7]
Fixing materials (5 screws and 5 wall plugs)
[8]
Set of printed documents for product documentation
[9]
5-core communication cable (optional accessory)
[10] 4 anti-vibration couplings for the outdoor unit
2.6
Product dimensions and minimum clearances
2.6.1
Indoor unit and outdoor unit
Figures 2 to 4.
2.6.2
Refrigerant lines
Key to figure 5:
[1]
Gas-side pipe
[2]
Liquid-side pipe
[3]
Siphon-shaped elbow as oil separator
If the outdoor unit is positioned higher than the indoor unit, install a
siphon-shaped elbow on the gas side after no more than 6 m and every
6 m thereafter ( Figure 5, [1]).
▶ Observe maximum pipe length and maximum difference in height
between indoor unit and outdoor unit.
Outdoor Unit
Maximum pipe
length
CL6001i 26 E
CL6001i 35 E
CL6001i 53 E
CL6001i 70 E
1) Gas side or liquid side
2) Measured from lower edge to lower edge.
Table 63 Pipe length and difference in height
Outdoor Unit
Liquid side [mm]
CL6001i 26 E
6.35 (1/4")
CL6001i 35 E
6.35 (1/4")
CL6001i 53 E
6.35 (1/4")
CL6001i 70 E
9.53 (3/8")
Table 64 Pipe diameter depending on unit type
Pipe diameter [mm]
6.35 (1/4")
9.53 (3/8")
12.7 (1/2")
15.9 (5/8")
Table 65 Alternative pipe diameter
50
Maximum difference
1)
2)
[m]
in height
[m]
≤ 25
≤ 10
≤ 25
≤ 10
≤ 30
≤ 20
≤ 50
≤ 25
Pipe diameter
Gas side [mm]
9.53 (3/8")
9.53 (3/8")
12.7 (1/2")
15.9 (5/8")
Alternative pipe diameter [mm]
6
10
12
16
Specification of the pipes
Min. piping length
Additional refrigerant to be added if the
pipe length exceeds 5 m (liquid side)
Piping Thickness
Thickness of insulation against heat
Material of insulation against heat
Table 66
2.7
Information on refrigerant
This device contains fluorinated greenhouse gases as refrigerant. The
device is hermetically sealed. You will find the information on the
refrigerant according to the Regulation (EU) No 517/2014 on
fluorinated greenhouse gases in the operating instructions of the device.
Information for the installer: If you refill refrigerant, enter the additional
charge size and the total charge size of the refrigerant in the table
"information on refrigerant" of the operating instructions.
3
Installation
3.1
Before installation
CAUTION
Risk of injury from sharp edges!
▶ Wear protective gloves during installation.
CAUTION
Danger of burns!
During operation the pipes become hot.
▶ Make sure, that the pipes cooled down before touching them.
▶ Check the scope of delivery for damage.
▶ Check whether a hissing sound due to negative pressure can be
detected when opening the pipes of the indoor unit.
3.2
Requirements for installation site
▶ Observe minimum clearances ( Figures 2 to 3).
Indoor Unit
▶ Do not install the indoor unit in a room in which open ignition sources
(for example: open flames, an operating wall mounted gas boiler or
an operating electric heating system) are in operation.
▶ The installation location must not be higher than 2000 m above sea
level.
▶ Keep the air inlet and air outlet clear of any obstacles to allow the air
to circulate freely. Otherwise poor performance and higher noise
levels may occur.
▶ Keep TV, radio and and similar appliances at least 1 m away from the
unit and the remote control.
▶ Mount the indoor unit on a wall that absorbs vibrations.
▶ Take minimum room area into account
Climate 6000i – 6721838270 (2024/01)
3 m
With Ø 6.35 mm (1/4"):
12 g/m
With Ø 9.53 mm (3/8"):
24 g/m
≥ 0.8 mm
≥ 6 mm
Polyethylene foam