LAK 3IMR - LAK 14ITR
4.1.1 Wall opening for split lines and
electric wires
Please proceed as follows when laying split lines and elec-
tric wires:
Drill a 70 mm opening for the pipework using a core drill
The opening for the pipework should be slightly inclined to-
wards the outdoor unit, so that no rainwater can penetrate
the building.
4.1.2 Wall opening for condensate drain
www.dimplex.de
4.1.3 Installation in coastal areas
NOTE
The air-to-water heat pump must NOT be installed in areas where
corrosive gases such as acids or alkaline gases can occur.
NOTE
If the outdoor unit is installed in a coastal area, direct sea wind should be
avoided.
Case 1: If the outdoor unit is installed in a coastal area, direct sea
wind should be avoided. Install the outdoor unit in the opposite
direction to the sea wind.
Case 2: If the outdoor unit is installed in the direction of the sea
wind, set up a wind guard to catch the sea wind.
The wind guard must be robust enough to catch the sea
wind (e.g. made from concrete).
The height and width of the wind guard must correspond to
at least 150% of the outdoor unit.
A distance of at least 700 mm from the outdoor unit must be
maintained to guarantee sufficient air flow.
Wind protection
NOTE
If the outlined requirements cannot be complied with during installation
in coastal areas, please contact Dimplex employees for more information
on corrosion protection.
NOTE
Dust or salt soiling on the heat exchanger should be regularly cleaned (at
least once a year) with water.
452162.66.09 · FD 9703
Sea wind
Sea wind
Sea wind
English
EN-5