Télécharger Imprimer la page

Dimplex LAK 9IMR Instructions D'installation Et D'utilisation page 26

Publicité

Les langues disponibles

Les langues disponibles

English
4
Outdoor unit
4.1 Installation
It is advisable to install the outdoor unit close to a wall, on a
foundation separate from the building with a minimum clear-
ance of 0.3 m on the intake side (Fig.4.1 + Fig.4.2).
If a canopy is mounted to protect from direct sunlight, rain or
snow it must not impede the heat exchange of the device.
In the case of a free-standing installation, the foundation is
to be connected on the intake side, flush with the device.
This will prevent snow from building up between the founda-
tion and the evaporator.
The minimum clearances (Fig.4.1) indicated must be ad-
hered to.
When selecting an installation location, it should be ensured
where possible that persons are not going to be inconven-
ienced by the circulation of warm/cold air or by noise emis-
sions.
The condensate tray offers various options for the conden-
sate drain. In warmer regions, the condensate can drain
from the device freely. In regions with longer periods of frost,
a controlled condensate drain is required.
Heat pump
Frost line
Condensate drain
Fig. 4.1
Heat pump
Frost line
Fig. 4.2
EN-4
0,3 m
0,3 m
Condensate drain
> 5%
452162.66.09 · FD 9703
Fig. 4.3
Installation on wall brackets is not advisable, as this frequently
leads to noise problems.
If this type of installation is used, observe the following instruc-
tions:
Fit rubber buffers
Take the weight of the outdoor unit into account
Ensure that the wall bracket is no higher than 1 m above the
ground
Ensure that minimum clearances are adhered to
Fig. 4.4
LAK 3IMR - LAK 14ITR
www.dimplex.de

Publicité

loading

Ce manuel est également adapté pour:

Lak 6imrLak 3imrLak 14imrLak 14itr