Alarms and faults
PROBLEM
LED POWER off
LED POWER off
The gate does not
open or close.
Example:
ALARM
POSSIBLE CAUSE
No power.
Fuses blown.
Input mains power voltage fault.
Control initialisation failed.
Fuse F1 blown or damaged.
This message is not visible if con-
troller is in battery power mode.
Overcurrent detected in inverter.
Incorrect connection to transfor-
mer SEC1-SEC2.
Travel data acquisition error.
Calibration procedure failed.
Automation system position
with parameter
Motor not connected.
Both limit switches activated.
Encoder not connected.
Severe encoder malfunction.
Check power cable.
Replace fuses. Always disconnect from mains
power before removing fuses.
Disconnect from mains power, wait 10 seconds
then reconnect to the mains and switch on. If the
problem persists, contact your local authorized
Pressing the TEST button it is possible to hide the
alarm temporarily and consult the control unit's
parameters.
Replace fuse.
Always disconnect from mains power before re-
Press the TEST button twice or perform 3 com-
mand requests in succession.
Swap connections between SEC1 and SEC2.
Check that open and closed limit switches are po-
sitioned correctly.
Press TEST and check if any safety devices are in
alarm state.
Repeat acquisition procedure.
Allow the indicated calibration times to elapse du-
ring self-acquisition.
Check that
before closing the release lock cover.
Repeat acquisition procedure.
SX
.
right hand opening gates
motor relative to passage seen from interior side).
If the position is changed and message
displayed:
• Move the gate into the closed position.
• Disconnect from mains power or remove the
main fuse and wait 5 seconds.
• Press and hold PROG until
appears on the display.
Repeat acquisition procedure.
Check the motor cable.
Check connections of limit switches or check for
foreign objects in limit switch blocks.
Check connection to encoder.
Replacing the encoder is recommended if the pro-
blem persists.
Press TEST button. If the error code is displayed
again, switch off the controller unit, wait 5 secon-
ds and switch on again. Replace the encoder if the
problem persists.
ACTION
DX
gates (position of
is
disappears and
79