Condominium function for partial open command (PED)
Disabled. The gate opens partially in step mode: open-stop-close-stop-open...
Enabled. Partial commands are ignored during gate opening.
Enabling operator present function
Disabled.
Enabled. The open (AP) or close (CH) button must be pressed continuously to operate the gate. The gate stops when
the button is released.
Gate open indicator / photocell test function and "battery saving"
The indicator is off when the gate is closed, and steadily lit during manoeuvres and when the gate is open.
quickly during closing manoeuvres.
If the gate is stopped in an intermediate position, the lamp extinguishes twice every 15 seconds.
Set
if the output SC
Set to
if the output SC
When the gate is completely open or closed, the controller unit deactivates any accessories connected to terminal SC
to reduce battery consumption.
Set to
if the output SC
Setting deceleration during opening and closing
See chapters 14 and 15
01= the gate decelerates near the limit switch ... 05= the gate decelerates long before the limit switch.
Setting gate open limit switch constant speed approach distance
N.B.: the manoeuvre speed is set with parameter
switch at constant speed.
Setting gate closed limit switch constant speed approach distance
N.B.: the manoeuvre speed is set with parameter
switch at constant speed.
01= last 3 cm; 02= last 6 cm; ... 40= last 120 cm.
Approximate example: 100 cm distance = value
Partial opening adjustment (%)
N.B.: This parameter is set to 50% (half of total gate travel) by default.
From 10% to 99% of total gate travel.
Type of signaling provided by COR output
STANDARD operation managed by parameter
Contact closed if the control unit is working properly.
Contact open if central locked in alarm.
Contact closed if the control unit is powered by the mains or charged battery.
Open contact due to a fault: control unit powered by low battery (voltage level set by par.
(the control unit no longer accept commands).
Closed contact if none of the fault related situations 1 and 2 occurs.
Open contact if at least one of the fault related situations 1 and 2 occurs
Closed contact if the gate is not completely open.
Open contact if the gate is completely open.
Closed contact if the gate is not completely closed.
Open contact if the gate is completely closed.
Setting automatic closing time
The timer starts from the gate open state and continues for the set time. Once the set time is reached, the gate closes
automatically. The timer count restarts if a photocell is triggered.
Pause time settable from 00 to 90 s.
Pause time settable from 2 to 9 min.
. After decelerating, the gate completes the distance to the limit
. After decelerating, the gate completes the distance to the limit
.
) or with error alert
69