Command
F8
[2-3P]
Obstruction
F9
detection with
motor stopped
Gate open si-
F10
gnaling output
F11 Encoder
F12 Soft Start
Sensor type
F14
selection
F18 Additional light
Automatic
F19
Closing Time
Automatic
closing time
F20
after partial
opening
Pre-flashing
F21
time
Gate travel
F28
speed
Slow-down
F30
speed
Travel sensi-
F34
tivity
From the control device connected to 2-3P, it performs a partial (1) or total opening (2)
of the gate.
The partial opening time is adjusted on function F 71.
1 = Partial opening / 2 = Open
With the gate closed, opened or totally stopped, the gearmotor stays idle if the safety
devices, that is, photocells or sensitive safety-edges detect an obstruction.
OFF = Deactivated (default) / ON = Activated
It signals the gate status. The signal device is connected to contact 10-5.
0 = lit when gate is open or moving (default) / 1 = during openings it flashes
intermittently each half second, and during closings it flashes intermittently
each second.
It stays on steadily when the barrier is open, off or when it s closed.
Managing slow-downs, obstruction detections and sensitivity.
OFF = Deactivated / ON = Activated (default)
With each opening and closing command, the gate starts moving slowly for a few
seconds.
OFF = Deactivated (default) / ON = Activated
Setting the type of accessory for controlling the operator.
0 = command with transponder sensor or magnetic card reader / 1 = command with
keypad selector (default).
Output on contact 10-E.
Flashing light: it flashes during the gate's opening and closing phases.
Cycle: outdoor lamp for extra lighting in the driveway. It stays lit from when the gate
starts opening to when it closes, including the waiting time prior to automatic closing
(only with with TCA activated).
0 = Flashing light (default)/ 1 = Cycle
The automatic-closing wait starts when the opening limit switch point is reached and
can be set to between 1 and 180 seconds. The automatic closing does not work if any
of the safety devices trigger when an obstruction is detected, or after a total stop, or
during a power outage.
OFF = Deactivated (default) / 1 = 1 180 = 180 seconds
The wait before the automatic closing starts after a partial opening command for an
adjustable time of between 1 s and 180 s.
The automatic closing does not work if any of the safety devices trigger when an
obstruction is detected, or after a total stop, or during a power outage.
The F19 function must not be activated.
OFF = Deactivated / 1 = 1 10 = seconds (default) / ... / 180 = 180 seconds
Adjusting the pre-flashing time for the flashing light connected to 10-E before each
maneuver. The flashing time is adjustable from one to ten seconds.
OFF = Deactivated (default) / 1 = 1 seconds / ... / 10 = 10 seconds
Setting the gate's opening and closing speeds, calculated as a percentage.
60 = Minimum speed / ... / 100 = Maximum speed (default)
Setting the gate's opening and closing slow-down speed, calculated as a percentage.
10 = Minimum speed / ... / 50 = Maximum speed (default)
Adjusting obstruction detection sensitivity during gate-leaf travel.
10 = maximum sensitivity / ... / 100 = minimum sensitivity (default)