3.3.4 Programming field 3 : Select Can address
Setting
0
1
2
3
4
5
6
7
It is possible to parallel several modules (one master with a maximum of three slaves), all the
slaves X will synchronize with the master X. Each module must have a different address.
3.3.5 Programming field 4 : offset on BOOST voltage
Setting
0
1
2
3
4
5
6
7
3.3.6 Programming field 5 : offset on FLOAT voltage
Setting
0
1
2
3
4
5
6
7
CHARGER_Frame1
Can address
0x0002 9000 master 0
0x0002 9001 master 1
0x0002 9002 master 2
0x0002 9003 master 3
0x0002 9004 slave 0
0x0002 9005 slave 1
0x0002 9006 slave 2
0x0002 9007 slave 3
12V output
Offset in mV
Offset in mV
-400
-300
-200
-100
0
100
200
300
12V output
24V output
Offset in mV
Offset in mV
-400
-300
-200
-100
0
100
200
300
Setting
8
9
10
11
12
13
14
15
24V output
36V output
Offset in mV
-800
-600
-400
-200
0
200
400
600
36V output
Offset in mV
-800
-600
-400
-200
0
200
400
600
CHARGER_Frame1
Can address
0x0002 9008 slave 0
0x0002 9009 slave 1
0x0002 900A slave 2
0x0002 900B slave 3
0x0002 900C slave 0
0x0002 900D slave 1
0x0002 900E slave 2
0x0002 900F slave 3
48V output
Offset in mV
-1200
-1600
-900
-600
-300
0
300
600
900
48V output
Offset in mV
-1200
-1600
-900
-600
-300
0
300
600
900
-120
-800
-400
0
400
800
1200
-120
-800
-400
0
400
800
1200