Operation type
Graphical display, see page 6
Fixed operation type: If the temperature in the duct is...
- lower than the set target value T1, then the blades are set in the position of W1.
This is usually set so that the air jet is directed upwards.
- between the target values T1 and T3, then the blades are set in the direction of W2.
This is usually set so that the air jet blows out straight.
- higher than the set target value T3, then the blades are set in the position of W3.
This is usually set so that the air jet is directed downwards.
Controlled operation type: If the temperature in the duct is...
- lower than the set target value T1, then the blades are set in the position of W1.
This is usually set so that the air jet is directed upwards.
- between the target values T1 and T2, then the blade position is a linear interpolation
between W1 and W2.
- between the target values T2 and T3, then the blade position is a linear interpolation
between W2 and W3.
- higher than the set target value T3, then the blades are set in the position of W3.
This is usually set so that the air jet is directed downwards.
Manual operation type:
The temperature-dependent control can be switched to manual activation on the touch panel.
The blow-out position required is now set via position control W5.
The set values T1 and T3 do not have any effect on the blade setting.
Inbetriebnahmeanleitung DGVAR-STG3-VAR
Start-up Instructions DGVAR-STG3-VAR
Instruction de mise en service DGVAR-STG3-VAR
5