Configuration DIP Switches
Modbus
BACnet
DIP
Position
1
Modbus
BACnet
2-4
A
B
Off
Off
Off
Off
Off
On
Off
On
On
Off
On
Off
On
On
On
On
5
Parity Even
Parity None
6
Non-Metric
Metric
7
Not used
8
Not used
10
All manuals and user guides at all-guides.com
A B
C
ON
2 3 4 5 6 7 8
1
Baud
Rate
Setting
Modbus protocol in use.
BACnet protocol in use.
C
Serial line baud rate
Off
Automatic (default)
On
4800
Off
9600
On
19200
Off
38400
On
57600
Off
76800
On
115200
Parity even (8E1).
Only affects Modbus protocol.
Parity none (8N2).
Only affects Modbus protocol.
Use non-metric units (°F).
Only affects display and service port.
Use metric units (°C).
Only affects display and service port.
Parity Even
Non-Metric
Metric
Parity None