Connecting Several Transmitters
Set the RS-485 termination jumper to "ON" on the
transmitter that is at the end of the line. This terminates
the line with a 120 Ω resistor. For location of the jumper,
see section Transmitter Body on page 4.
Connect the cable shield to ground on the building
controller side.
Building controller
Power
+Vs
supply
-Vs
D+
RS-485:
BACnet or
D-
Modbus
master
GND
SHIELD
Connect shield on controller side
Transmitter
Transmitter
+Vs
-Vs
D+
D-
GND
Shld
Transmitter
+Vs
+Vs
-Vs
-Vs
D+
D+
D-
D-
GND
GND
Shld
Shld
Set RS-485
termination jumper
EN
9