values
Code description
(bold = default)
p05 Long automatic
0 to 99 ( time delay value
closing time delay in
0: 0 s
pedestrian cycle
p07 Cell safety input
0: inactive
1: active
2: active with autotest via test output
3: active with autotest via power
supply switching
4: bus cells
p09 Programmable safety
0: inactive
input
1: active
2: active with autotest via test output
3: active with autotest via power
supply switching
p10 Programmable safety
0: active closing
input - function
1: active opening
2: active closing + ADMAP
3: all movement disabled
p11 Programmable safety
0: stop
input - action
1: stop + partial reversal
2: stop + complete reversal
p12 Orange warning light 0: no warning
1: with 2 s warning prior to movement
p13 Area lighting output
0: inactive
1: controlled operation
2: automatic + controlled
operation
p14 Area lighting time
0 to 60 (time delay value = value x 10 s)
delay
6: 60 s
p15 Auxiliary output
0: inactive
1: automatic: gate open indicator light
2: automatic: timed bistable
3: automatic: one-touch
4: controlled: bistable (ON-OFF)
5: controlled: one-touch
6: controlled: timed bistable
p16 Auxiliary output time
0 to 60 (time delay value = value x 10 s)
delay
6: 60 s
p17 Lock output
0: active 24v one-touch
1: active 12V one-touch
p18 Lock release
0: inactive
1: active
p19 Closing speed
1: slowest speed
at
10: fastest speed
default value:
- Control Box 3s Axovia io: 5
p20 Opening speed
- Control Box 3s Ixengo io: 6
p21 Closing slowdown
0: shortest slowdown zone
zone
at
5: longest slowdown zone
default value: 1
p22 Opening slowdown
0: shortest slowdown zone
zone
at
5: longest slowdown zone
default value: 1
13
Setting
completed
= value x 5 min)
Comments
Value 0 must be selected if the short automatic closing time delay in pedestrian cycle is
active.
0: the safety input is not taken into account.
1: safety device without autotest; it is essential to check that it is operating correctly every 6
months.
2: the autotest is run on the device for each operating cycle via the test output,
reflex cell application with autotest.
3: the autotest is run on the device for each operating cycle via power supply switching of
the cell power supply output (terminals 21 and 22).
4: bus cells application.
0: the safety input is not taken into account.
1: safety device without
auto-test.
2: the autotest is run on the device for each operating cycle via the test output
3: the autotest is run on the device for each operating cycle via power supply switching of
the cell power supply output (terminals 21 and 22).
0: the programmable safety input is only active when closing.
1: the programmable safety input is only active when opening.
2: the programmable safety input is only active when closing and, when activated, the gate
cannot be opened.
3: emergency stop application; if the programmable safety input is activated, the gate cannot
be moved.
0: emergency stop application, compulsory if p10=3
disabled if a safety edge is connected to the programmable safety input
1: recommended for safety edge application
2: recommended for cell application
If the gate opens onto a public path, the "with warning" configuration must be selected:
P12=1.
0: the area lighting output is not taken into account.
1: the area lighting is remotely controlled.
2: the area lighting is remotely controlled when the gate is stationary + the area lighting
comes on automatically when the gate is moving, and remains on when it stops moving
for the duration of the time delay programmed in parameter "p14".
p13=2 is compulsory for operation in automatic mode.
If value 0 is selected, the area lighting goes out as soon as the gate stops moving.
0: the auxiliary output is not taken into account.
1: the gate indicator light is off when the gate is closed, flashing when the gate is moving and
on when the gate is open.
2: output activated when movement starts, during movement then deactivated at the end of
the time delay programmed in parameter "p16".
3: one-touch at contact when movement starts.
4: operation changes as follows each time the memorised button on the radio control point is
pressed: ON, OFF, ON, OFF...
5: one-touch at contact by pressing the memorised button on the radio control point.
6: output activated by pressing the memorised button on the radio control point then
deactivated at the end of the time delay programmed in parameter "p16".
The auxiliary output time delay is only active if the value selected for P15 is 2 or 6.
The lock is released at the start of opening.
0: the lock release is inactive.
1: recommended for use with an electric lock.
This parameter is only available on Control Box 3S Axovia io models.
If this parameter is modified, the installer must check that the limitation of forces complies
with appendix A of the standard EN12 453 or install a safety edge.