2.6
Combustion chamber pressure
The combustion chamber pressure is the same as for natural
gas.
2.7
Gas pressure and output
measured at the coupling with combu-
Pressure:
stion chamber at 0 mbar. If the combu-
stion
required gas-pressure is that shown on
the diagram plus the pressurization va-
lue.
Example: in order to develop 350 kW it is
necessary to have a 14 mbar at the cou-
pling with the chamber at 0. Should the
combustion chamber be pressurized at
+3 mbar, the required pressure is
14 + 3 = 17 mbar.
maximum output obtainable with:
Output:
–
–
Tab. A indicates the minimum pressure drops along the gas sup-
ply line, depending on the maximum burner output.
All manuals and user guides at all-guides.com
chamber
is
pressurized,
gas with a net heat value of 22.200
kcal/m3;
gas ring set as indicated in the
Gas 4, Gas 4/2 and Gas 4 P/M tech-
nical instructions under the para-
graph "Combustion - Head Setting".
LPG kit
For pressure levels different from those indicated
above, please contact the Technical Office.
WARNING
Combustion chamber pressure
the
kW
180
212
244
277
309
341
373
406
3
GB
D1336
Burner output
1 p (mbar)
G31
5.5
7.1
8.7
10.4
12
13.6
15.2
16.8
D1337
Fig. 2
Fig. 3
Tab. A
2915327