Télécharger Imprimer la page

Riello Gulliver RG3D TL Instructions Pour Installation, Utilisation Et Entretien page 68

Publicité

Les langues disponibles

Les langues disponibles

5.1
CONTROL BOX VISUAL DIAGNOSTIC
The control box has a diagnostic function that can identify the likely causes of any malfunctions (indicator:
RED LED).
In order to be able to use this function, press and hold the reset button for at least 3 seconds from when the
appliance is made safe (lock-out).
The control box sends a sequence of pulses that are repeated at 2-second intervals.
RED LED illuminated
press reset for 3 sec.
The sequence of pulses issued by the control box identifies the possible types of malfunction, which are
listed in the table below.
SIGNAL
2 pulses
4 pulses
7 pulses
8 pulses
ATTENTION
To reset the control box after the diagnostics display, press the lockout-reset button.
3363
The flame does not stabilise at the end of the safety time:
– flame detector faulty or dirty;
– oil valve faulty or dirty;
– faulty ignition transformer;
– poor burner regulation.
Light present in the chamber before the burner's switching on or off:
– presence of a strange light before or after the limit thermostat switching
over;
– presence of a strange light during pre-purging;
– presence of a strange light during post-ventilation.
Loss of flame during operations:
– poor burner regulation (insufficient gas);
– oil valve faulty or dirty;
– flame detector faulty or dirty.
Check and monitor oil heater (if fitted):
– heater or control thermostat faulty.
Interval
Pulses
PROBABLE CAUSE
15 GB
2s
Pulses

Publicité