Télécharger Imprimer la page

Briggs & Stratton 100SED Serie Guide D'installation Et De Démarrage Rapide page 24

Publicité

Les langues disponibles

Les langues disponibles

Product Specfications
Model 071048
Series 100SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................100 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
22,000 RMS Symmetrical Amperes on Utility Side
.................................
10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................13 kg (29 lbs)
Model 071049
Series 200SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................200 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
25,000 RMS Symmetrical Amperes on Utility Side
.................................
10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................27 kg (59 lbs)
Model 071068, 071246
Series 200SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................200 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
25,000 RMS Symmetrical Amperes on Utility Side
.................................
10,000 RMS Symmetrical Amperes on Generator Side
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................27 kg (59 lbs)
This transfer switch is a UL Listed device.
24
Automatic Transfer Switch
Model 071054
Series 200SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................200 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
.................................
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................27 kg (59 lbs)
Model 071070, 071248
Series 200SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................150 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
.................................
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................27 kg (59 lbs)
Model 071071, 071247
Series 100SED
Rated Maximum Load Current
a 25°C (77°F)* ..............................................................100 Amps
Rated AC Voltage. ..............................................................250 Volts
Poles ...............................................................................................2
Frequency ................................................................................60 Hz
Fault Current Rating ..........
.................................
Normal Operating Range ............... -28.8°C (-20°F) to 40°C (104°F)
Weight ........................................................................13 kg (29 lbs)
25,000 RMS Symmetrical Amperes on Utility Side
10,000 RMS Symmetrical Amperes on Generator Side
25,000 RMS Symmetrical Amperes on Utility Side
10,000 RMS Symmetrical Amperes on Generator Side
22,000 RMS Symmetrical Amperes on Utility Side
10,000 RMS Symmetrical Amperes on Generator Side
BRIGGSandSTRATTON.COM

Publicité

loading