INSTALLATION MANUAL
Installation cover's rope
Tap Screw

Drainage test

Drainage test
Check whether the drainpipe is unhindered.
New built house should have this test done before paving
the ceiling.
<300mm
Models 12 to 18:
Operate the air conditioner in "COOLING" mode. The sound of
the drain pump shall be heard. Check whether the water is
discharged well (1 min lag is possible, according to the length of
the drain pipe), and check whether the water leaks from the
joints.
Power off the air conditioner and recover the cap.
Models 24 to 60:
Remove the test cover, and stow about 2000ml water to the
water pan.
Operate the air conditioner in "COOLING" mode. The sound of
the drain pump shall be heard. Check whether the water is
discharged well (1 min lag is possible, according to the length of
the drain pipe), and check whether the water leaks from the
joints.
Power off the air conditioner and recover the cap.
Loosen upper nut
Adjust lower nut
Fig.1-13
Slide the four sliders
in the corresponding
channel when installing
the cover
Fig.1-14
1-1.5m
Lean over 1/50
Pump-pipe clasp
(the fittings)
Fig.1-15
Models 24 to 60:
Test cap
All the pictures in this manual are for explanation purpose only.
They may be slightly different from the air conditioner you
purchased(depend on model).The actual shape shall prevail.
1.4

Fresh air intake

Models 12 and 18:
Models 24 to 60:
Ø75mm
80mm
Fresh air intake
(75 mm)
50
Fig.1-16
NOTE
Fig.1-17
Fig.1-18