SETTING THE AIR ADJUSTMENT PLATE
A) The hydraulic AIR SHUTTER (1) is operated by the
HYDRAULIC JACK (6), assuring complete opening of the
combustion air intake.
Regulation of the combustion air flow is made by
adjustment of the manual AIR ADJUSTMENT PLATE (4)
after loosening the FIXING SCREWS (3 & 5).
The initial setting of the air adjustment plate should be
made according to Column 5 in the Burner Set-up Chart.
B) The proper number on the manual AIR ADJUSTMENT
PLATE (4) should line up with the SETTING INDICATOR
(2) on the fan housing cover.
Once set, the air adjustment plate should be secured in
place by tightening SCREWS 3 and 5.
Manually open and release the hydraulic air shutter to
ensure it has free movement.
C) The final position of the air adjustment plate will vary on
each installation. Use instruments to establish the proper settings for maximum CO
NOTE:
Variations in flue gas, smoke, CO
Therefore, the burner cover must be in place when making the final combustion instrument readings, to ensure proper
test results.
2902451
and temperature readings may be experienced when the burner cover is put in place.
2
1
2
3
D5775
11
and a smoke reading of zero.