Performances
AQUATOP T..H eau-eau (selon données EN14511)
AQUATOP T..H
R 407c
Modèle
T
WL
VL
°C
kW
35
22.9
40
22.4
45
22.0
T17CH
50
21.5
55
21.1
60
20.8
35
25.9
40
25.8
45
25.7
T22H
50
25.6
55
25.6
60
24.5
35
35.5
40
35.5
45
35.5
T28H
50
34.9
55
34.2
60
33.6
35
48.9
40
48.1
45
47.4
T35H
50
46.7
55
46.0
60
45.7
35
58.6
40
57.6
45
56.6
T43H
50
55.5
55
54.5
60
53.3
T
: Température de départ de l'eau de chauffage
VL
WL: Puissance thermique
KL: Puissance frigorifique
AL: Puissance absorbée
68
Température d'entrée d'eau [°C]
10
KL
AL
COP
kW
kW
-
18.9
4.0
5.7
18.0
4.5
5.0
17.0
5.0
4.4
16.0
5.6
3.9
14.9
6.2
3.4
14.0
6.8
3.1
21.2
4.7
5.5
20.5
5.3
4.9
19.8
6.0
4.3
19.0
6.6
3.9
18.3
7.3
3.5
16.3
8.1
3.0
28.5
7.0
5.1
27.9
7.6
4.7
27.3
8.3
4.3
25.9
9.0
3.9
24.5
9.7
3.5
23.1
10.4
3.1
39.7
9.2
5.3
38.1
10.1
4.8
36.5
10.9
4.4
35.0
11.8
4.0
33.4
12.6
3.7
32.0
13.6
3.4
47.3
11.3
5.2
45.3
12.3
4.7
43.3
13.3
4.3
41.2
14.3
3.9
39.2
15.3
3.6
36.7
16.7
3.2
15
WL
KL
AL
kW
kW
kW
25.5
21.9
3.7
25.1
20.8
4.3
24.7
19.7
4.9
24.2
18.7
5.5
23.8
17.6
6.1
23.4
16.7
6.7
27.1
22.4
4.7
27.1
21.7
5.3
27.0
21.0
6.0
27.0
20.3
6.6
26.9
19.6
7.3
25.8
17.6
8.2
42.3
35.2
7.1
41.1
33.3
7.8
40.0
31.5
8.5
38.9
29.7
9.2
37.7
27.8
9.9
36.6
26.0
10.6
52.7
43.2
9.5
52.3
42.0
10.3
52.0
40.8
11.2
51.6
39.5
12.1
51.3
38.3
13.0
50.9
36.8
14.1
63.4
51.7
11.7
62.4
49.7
12.7
61.4
47.7
13.7
60.3
45.7
14.6
59.3
43.7
15.6
58.0
41.0
17.0
COP
-
6.9
5.8
5.0
4.4
3.9
3.5
5.8
5.1
4.5
4.1
3.7
3.2
6.0
5.3
4.7
4.3
3.8
3.4
5.6
5.1
4.6
4.3
3.9
3.6
5.4
4.9
4.5
4.1
3.8
3.4