AERMEC MODUCONTROL Manuel D'utilisation page 40

Réglage électronique
Masquer les pouces Voir aussi pour MODUCONTROL:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Index - String
MIN value
-20 °C
6 SF1
Index - String
MIN value
-40 °C
7 tF1
Index - String
MIN value
-20 °C
8 SF2
Index - String
MIN value
-40 °C
9 tF2
Index - String
MIN value
A SC1
25 °C
Index - String
MIN value
b tC1
-40 °C
Index - String
MIN value
C SC2
25 °C
Index - String
MIN value
d tC2
-40 °C
Index - String
MIN value
E SA5
25 °C
40
Setting cooling temperature setpoint 1
MAX value
This parameter indicates the maximum value of the cooling setting, corresponding with the minimum outside air
26 °C
temperature (index (7) user menu). This parameter is only visible if the compensation function has been activated
(index (5) user menu).
Setting the outside air temperature 1
MAX value
This parameter indicates the minimum outside air temperature taken into consideration for cooling compensation.
50 °C
This parameter is only visible if the compensation function has been activated (index (5) user menu).
Setting cooling temperature setpoint 2
MAX value
This parameter indicates the minimum value of the cooling setting, corresponding with the maximum outside air
26 °C
temperature (index (9) user menu). This parameter is only visible if the compensation function has been activated
(index (5) user menu).
Setting the outside air temperature 2
MAX value
This parameter indicates the maximum outside air temperature taken into consideration for cooling compensation.
50 °C
This parameter is only visible if the compensation function has been activated (index (5) user menu).
Setting heating set 1
MAX value
This parameter indicates the maximum value set at heating, in correspondence with the minimum outdoor air tem-
perature (user menu index (b) This parameter is visible only if the compensation function is activated (index (5) user
menu).
(*)
(*):
- the maximum limit can be configured via the parameter (t) of the installer menu;
- if the parameter (8) of the installer menu is set at 4, the maximum limit becomes 70°C in order to allow insertion of a
set-point for boiler adjustment;
Setting the outside air temperature 1 (heating)
MAX value
This parameter indicates the minimum outside air temperature taken into consideration for heating compensation.
50 °C
This parameter is only visible if the compensation function has been activated (index (5) user menu).
Setting heating set 2
MAX value
This parameter indicates the minimum value set at heating, in correspondence with the maximum outdoor air tem-
perature (user menu index (c) This parameter is visible only if the compensation function is activated (index (5) user
menu).
(*)
(*):
- the maximum limit can be configured via the parameter (t) of the installer menu;
- if the parameter (8) of the installer menu is set at 4, the maximum limit becomes 70°C in order to allow insertion of a
set-point for boiler adjustment;
Setting the outside air temperature 2 (heating)
MAX value
This parameter indicates the maximum outside air temperature taken into consideration for heating compensation.
50 °C
This parameter is only visible if the compensation function has been activated (index (5) user menu).
MAX value
The heat pumps have a work set for the production of DHW; this set indicates the produced water temperature above
which the compressor is stopped. Remember that to display this set, the parameter (A) of the installer menu must be
active (value set = 1).
(*):
(*)
- the maximum limit can be configured via the parameter (t) of the installer menu;
- if the parameter (8) of the installer menu is set at 4, the maximum limit becomes 70°C in order to allow insertion of a
set-point for boiler adjustment;
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Setting DHW set
Parameter function
22/10 – 6343841_04