Operating via AMS Device Manager
AMS Device Manager is a software package designed to commission and maintain field devices.
Please consult the operating instructions or online help for details on using AMS Device
Manager. You can find more information at: http://www.emersonprocess.com/AMS/.
Electronic Device Description (EDD)
SITRANS LR250 requires the EDD for AMS Device Manager version 9.0.
Configuring a new device via AMS Device Manager
1)
Check the product page of our website at: www.siemens.com/LR250 to make sure you
have the most recent EDD. Go to Support > Software Downloads and if necessary
download it. Save the files to your computer, and extract the zipped file to an easily
accessed location.
2)
Launch AMS Device Manager– Add Device Type, browse to the unzipped EDD file and
select it.
Launch AMS Device Manager. An Application Guide for setting up HART devices with AMS
Device Manager can be downloaded from the product page of our website under Support
Maintenance
SITRANS LR250 requires no maintenance or cleaning under normal operating conditions. If
cleaning becomes necessary under severe operating conditions:
1)
Note the antenna material and the process medium, and select a cleaning solution that
will not react adversely with either.
2)
Remove the device from service and wipe the antenna clean using a cloth and suitable
cleaning solution.
Unit Repair and Excluded Liability
For detailed information, please see the inside back cover.
Antenna or electronics/enclosure replacement
• If the antenna requires replacement due to damage or failure, it may be replaced without
the need for re-calibration.
• Changing to a different antenna type may be performed by a Siemens authorized repair
center or personnel.
• If the electronics or enclosure require replacement due to damage or failure, plesase
ensure the correct antenna version is used, otherwise a re-calibration will need to be
performed by Siemens authorized personnel.
Page EN-22
SITRANS LR250 (HART) – QUICK START MANUAL
A5E31997170