•
Combined stage. (only available in installations with AZCE6OUTPUT8 modules) Enables activating and deactivating
the combined stage of the "Control Stages" parameter in the user's Zone Settings Menu.
•
Hysteresis Configuration. Defines the temperature differential between the room temperature and the set-point
temperature required to start applying the Algorithm RadianT. This algorithm prevents overheating in underfloor air
conditioning installations. If your installation has radiators, set this value to 0ºC. (By default 0ºC)
•
Type of opening. Use this parameter to configure the type of opening of the damper output.
*Note: If you change this parameter, all the dampers of the installation will be affected. It is not recommended for RINT
and RIC intelligent grilles.
•
Standby mode (only for Blueface thermostats). Configuration of the operating logic of the motorized elements when
there is no demand on the system. This is disabled by default.
•
Relay settings. Use this parameter to change the operation logic of the CMV/Boiler of the system main control board.
(By default CMV)
•
(only available for installations with AZX6SONDPROTEC) (Not available on 3.5.0
Return temperature
AZCE6THINKR)
. Defines the cut-off temperatures of the system for both heating (32ºC, 34ºC and 36ºC) and cooling
mode (6ºC, 8ºC and 10ºC) in order to protect the AC unit. It is set by default in 34ºC in heating mode and 8ºC in cooling
mode.
•
(only for Think thermostats)
Q-Adapt
In direct expansion units. Select the control algorithm that best fits your installation. These are the available options:
-
Maximum: the system operates at maximum speed, irrespective of the number of zones.
-
Power: the speed of the system is higher than in standard mode to increase the flow.
-
Standard (by default): the system automatically regulates the speed based on the number of zones.
-
Silence: the speed of the system is lower than in standard mode to reduce the noise.
-
Minimum: the system operates at minimum speed, irrespective of the number of zones.
In 0-10 V Fancoil units. Allows to control the minimum (1.5 V by default) and maximum (10 V by default) working fan
voltage of the controlled unit, in steps of 0.1 V. The minimum voltage corresponds with the desired lowest speed for
the unit and the maximum voltage corresponds with the highest speed. The medium speed corresponds with the mid
point between both of them.
•
Radio channel. It activates/deactivates the wireless association module of the system.
•
(only for Think thermostats)
Information
Webserver.
•
(only available for master thermostat Blueface)
Reset system
reconfigure the thermostats, please check
•
Centralized Controller. It allows defining whether or not your installation has a Centralized Controller. By default it
will be disabled.
•
(only in installations with AZX6BACNET).
BACnet
the subnet mask and the Gateway IP and allows you to modify them. Press on the value you want to change, modify
it and then press to confirm. The values by default are:
-
Device ID: 1000
-
Port: 47808
-
IP Address: DHCP
•
(only available in Blueface thermostats and if the system detects an H2 error in the indoor unit).
Protection mode
allows you to disable the delay in the closing of the motorized elements.
.
. It provides information about the zone, the system, the devices and the
. Resets the system and returns to factory settings. To
Initial setup
).
This parameter displays the Device ID, the uplink port, the IP address,
ES
EN
FR
IT
PT
ersion
v
DE
This
31