WORKING FIELD TBG 45PN / 60PN
E
N
G
L
I
S
H
The working fields are obtained from test boilers corresponding to the standard EN267 and are indicatively for the combination burner-
boiler. For correct working of the burner the size of the combustion chamber must correspond to current regulations; if not the manufac-
turers must be consulted.

POWER SUPPLY LINE

The gas supply scheme is shown in the diagram below. The gas train is certified in accordance with regulations EN 676 and is supplied
separately from the burner.
A manual shut off valve and anti-vibration joint must be installed upstream of the gas valve, as shown in the diagram.
GENERAL GAS BURNER SYSTEM
Legend
1) Manual shut off valve
2) Anti-vibration joint
3) Gas filter
4) Minimum gas pressure switch
5) Safety valve
6) Pressure regulator
7) Valves seal control device (obligatory for burner with maxi-
mum nominal thermal out-put over 1200 kW)
Gas train
supplied by the manufacturer
8) Two-stage working valve
9) Control servomotor
10) Air adjustment gate
11) Air pressure switch
12) Combustion head
6 / 8
000608367_200806
The job of the installer