INSTALLATION MANUAL
UCA3
3-Door standalone controller (Radio/Proximity)
2] REMINDERS AND RECOMMENDATIONS
Installation Recommendations
To ensure secure installation,
do not forget to mount the varistor
on the locking mechanism and
in parallel with the power supply.
Recommended cables
3 Pair 0.6mm cable.
Recommended power supplies
The references of the power
supplies which are adapted for
use with the UCA3 are: ARD12
and BS60. If it is a "shear lock"
locking system, it must have
a separate power supply.
3] PACKAGE CONTENTS
Central unit Screw cover
UCA3
1
4] ASSEMBLY
WARNING
Do not use switch mode power
supplies which may cause harmful
interference
and
functioning of the tag readers.
Readers
The distance between the auxiliary
readers and the UCA3 central
control unit must be between
60CM and 50M (minimum cable
cross-section 7 x 0.6 mm²).
Radio aerial
A rigid wire (1.5 mm² cross-section
and 17.3 cm in length), must be
Aerial
USB cable
17.3 cm
1
1
connected to the terminal 2 on
the UCA3 to ensure good quality
reception. A remote aerial may
prevent
correct
also be connected to the terminals
"1" and "2" on the UCA3:
- "1" = Woven shield inside
coaxial cable,
- "2" = Central core of the coaxial
cable.
Distance between central units
The minimum distance between
two UCA3 central units must be
1M in order to avoid any radio
frequency and electromagnetic
interference.
Wood screw
Wall plug
4x60
(S6)
1
4
User Guide
CD-ROM
4
1
cdvi.com
cdvigroup.com
EN
2
3