Warning
Remove the mains plug from the
socket and shut off the gas supply
during repair.
6.1
Troubleshooting table
/i
Fault
The heater does not 1
start up.
The heater triggers a
fault; the red lamp on
the operating panel
lights up.
22
Cause
The heater has no volt-
age.
2
The fan motor runs
heavily or is blocked.
3
The thermostat is set to Correct the settings.
a too low temperature.
4
There is no through-
connector on the ther-
mostat connection.
5
Defect in the operating
panel
6
The mains plug has
been incorrectly inserted
into the socket.
7
The earth of the socket
is not OK.
40.020.947 - rev. 01 - 2007
Solution
Check the electrical connec-
tion.
Check if the fan motor is dirty
or blocked.
Replace the fan motor.
Fit the through-connector.
Repair or replace the operat-
ing panel
Reverse the plug.
Have the earth of the socket
check by a recognised
installer.
Action
User
User
Dealer
User
User
Dealer
User
User
GA 42-60-85-110